Worked example
Example: Insulated 15 m digester, mild climate. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Sludge feed | 40,000 kg/d |
| Sludge specific heat | 4.2000 kJ/(kg·K) |
| Digester temperature | 37.000 °C |
| Incoming sludge temperature | 18.000 °C |
| Diameter | 15.000 m |
| Side water depth | 8.0000 m |
| Depth at the centre (cone floor) | 10.000 m |
| Wall coefficient | 0.50000 W/(m²·K) |
| Earth or air next to the wall | 10.000 °C |
| Floor coefficient | 1.2000 W/(m²·K) |
| Earth below the floor | 12.000 °C |
| Roof coefficient | 0.80000 W/(m²·K) |
| Air above the roof | 5.0000 °C |
| Sludge density | 1,000.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sludge heating | 36.944 kW |
| Wall loss | 5.0894 kW |
| Floor loss | 5.4867 kW |
| Roof loss | 4.5239 kW |
| Heat exchanger duty | 52.044 kW |
| Daily heat | 4.4966 GJ |
| Digester volume | 1,531.5 m³ |
| Temperature drop in 24 h without heat | 0.69906 K |
Open this example in the calculator and change any input.
Formula
\(q_s = \dot mc_p(T_d - T_s), \quad q = UA\,\Delta T\ \text{(wall, floor, roof)}, \quad \Delta T_{24h} = \frac{Q_d}{\rho Vc_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Sludge feed | kg/s |
| \(c_p\) | Sludge specific heat | J/(kg·K) |
| \(T_d\) | Digester temperature | K |
| \(T_s\) | Incoming sludge temperature | K |
| \(D\) | Diameter | m |
| \(h_s\) | Side water depth | m |
| \(h_m\) | Depth at the centre (cone floor) | m |
| \(U_w\) | Wall coefficient | W/(m²·K) |
| \(T_{ew}\) | Earth or air next to the wall | K |
| \(U_f\) | Floor coefficient | W/(m²·K) |
| \(T_{ef}\) | Earth below the floor | K |
| \(U_r\) | Roof coefficient | W/(m²·K) |
| \(T_a\) | Air above the roof | K |
| \(\rho\) | Sludge density | kg/m³ |
| \(q_s\) | Sludge heating | W |
| \(q_w\) | Wall loss | W |
| \(q_f\) | Floor loss | W |
| \(q_r\) | Roof loss | W |
| \(q\) | Heat exchanger duty | W |
| \(Q_d\) | Daily heat | J |
| \(V\) | Digester volume | m³ |
| \(\Delta T\) | Temperature drop in 24 h without heat | K |
Method and standards
Digester heat balance.
Where it is used
- Heat exchanger and boiler sizing for digesters.
- Winter operation checks.
Common mistakes
- Leaving out the feed heating.
- Using air temperature against buried walls.
Assumptions and limits
- Steady losses; radiation included in U.
Questions and answers
Why is the sludge heating the largest part?
Thickened sludge is mostly water; raising 90 t/d by 25 K needs about 95 GJ a day, twice the conduction losses.
What do the defaults represent?
An illustrative case: Insulated 15 m digester, mild climate. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.