Worked example
Example: MLSS 3000, RAS 10 000. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Influent flow | 2,000.0 m³/d |
| MLSS | 3,000.0 mg/L |
| Return sludge concentration | 10,000 mg/L |
| Settled volume after 30 min (mL/L) | 300.00 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Return ratio X/(X_r − X) | 42.857 % |
| Return flow | 857.14 m³/d |
| Return ratio from settled volume | 42.857 % |
Open this example in the calculator and change any input.
Formula
\(R = \frac{X}{X_r - X}, \quad R_{SV} = \frac{SV_{30}}{1000 - SV_{30}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Influent flow | m³/s |
| \(X\) | MLSS | kg/m³ |
| \(X_r\) | Return sludge concentration | kg/m³ |
| \(SV_{30}\) | Settled volume after 30 min (mL/L) | - |
| \(R\) | Return ratio X/(X_r − X) | - |
| \(Q_r\) | Return flow | m³/s |
| \(R_{SV}\) | Return ratio from settled volume | - |
Method and standards
Solids balance.
Where it is used
- ETP control.
- Operator examinations.
Common mistakes
- Using SV in % with 1000.
- Ignoring the wasting stream.
Assumptions and limits
- Steady state.
References
- Clarifier solids balance R = X/(X_r − X) (growth and effluent solids neglected)
Questions and answers
MLSS 3000, return sludge 10,000 mg/L?
R = 0.43: about 857 m³/d of return.
Settled volume 300 mL/L?
R about 0.43, consistent here.
Thin return sludge?
Needs more return flow, loading the clarifier.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.