Equalisation Tank Volume from a Daily Flow Pattern

Equalisation tank volume to deliver a steady average outflow from six blocks of inflow over the day, from the largest swing of cumulative inflow minus outflow.

Refinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Six 4-hour blocksShift pattern, 2-hour blocks

Daily pattern

Results

The six blocks cover one day and the pattern is taken to repeat daily; use shorter blocks if flow changes faster.

Average outflow83.333m³/h
Storage needed400.00m³
Tank volume with allowance480.00m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Six 4-hour blocks. The inputs, in the units selected above:

InputValue
Block 1: inflow40.000 m³/h
Block 2: inflow60.000 m³/h
Block 3: inflow120.00 m³/h
Block 4: inflow140.00 m³/h
Block 5: inflow90.000 m³/h
Block 6: inflow50.000 m³/h
Length of each block4.0000 h
Allowance for dead volume and margin20.000 %

Applying the formula below gives:

ResultValue
Average outflow83.333 m³/h
Storage needed400.00 m³
Tank volume with allowance480.00 m³

Open this example in the calculator and change any input.

Formula

\(V_s = \max_k \sum_{i \le k}(Q_i - \bar Q)t_b - \min_k \sum_{i \le k}(Q_i - \bar Q)t_b\)

Variables

Symbol Meaning SI unit
\(Q_{1}\) Block 1: inflow m³/s
\(Q_{2}\) Block 2: inflow m³/s
\(Q_{3}\) Block 3: inflow m³/s
\(Q_{4}\) Block 4: inflow m³/s
\(Q_{5}\) Block 5: inflow m³/s
\(Q_{6}\) Block 6: inflow m³/s
\(t_b\) Length of each block s
\(k\) Allowance for dead volume and margin -
\(\bar Q\) Average outflow m³/s
\(V_s\) Storage needed m³
\(V\) Tank volume with allowance m³

Method and standards

Mass diagram.

Where it is used

  • ETP equalisation tanks.
  • Condensate and drain collection tanks.

Common mistakes

  • Averaging over a non-repeating period.
  • No dead volume.

Assumptions and limits

  • The six-block pattern (6 t_b long) repeats; with 4-hour blocks that is a daily pattern, with other block lengths the cycle is 6 t_b.

References

  • Mass-diagram method: storage = max − min of cumulative (inflow − average) (Metcalf & Eddy)

Questions and answers

Six 4-hour blocks of 40, 60, 120, 140, 90 and 50 m³/h?

Average 83.3 m³/h; storage 400 m³, about 480 m³ with 20 % allowance.

Why the cumulative curve?

The tank fills while inflow exceeds the average and drains when it is below.

Load equalisation?

Concentration peaks also flatten when the tank is mixed.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.