Chlorine Disinfection: CT Value and Contact Tank

CT achieved by a chlorine contact tank from residual, volume, flow and baffling factor (t₁₀), against a required CT, and the tank volume to meet it.

Sugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 1 mg/L, 400 m3, 10 000 m3/d, BF 0.50.5 mg/L, serpentine BF 0.7

Results

Baffling factors: 0.1 unbaffled, 0.3 poor, 0.5 average, 0.7 superior, 1.0 plug flow (US EPA guidance). Required CT depends on organism, log credit, pH and temperature.

Theoretical detention time57.600min
Effective contact time28.800min
CT achieved (mg·min/L)28.800
Ratio to the requirement0.96000
Tank volume to meet the requirement416.67m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 mg/L, 400 m3, 10 000 m3/d, BF 0.5. The inputs, in the units selected above:

InputValue
Free chlorine residual at the outlet1.0000 mg/L
Contact tank volume400.00 m³
Peak flow10,000 m³/d
Baffling factor t₁₀/T0.50000 -
Required CT (mg·min/L)30.000 -

Applying the formula below gives:

ResultValue
Theoretical detention time57.600 min
Effective contact time28.800 min
CT achieved (mg·min/L)28.800
Ratio to the requirement0.96000
Tank volume to meet the requirement416.67 m³

Open this example in the calculator and change any input.

Formula

\(T = \frac{V}{Q}, \quad t_{10} = BF\cdot T, \quad CT = C\,t_{10}, \quad V_{req} = V\frac{CT_{req}}{CT}\)

Variables

Symbol Meaning SI unit
\(C\) Free chlorine residual at the outlet kg/m³
\(V\) Contact tank volume m³
\(Q\) Peak flow m³/s
\(BF\) Baffling factor t₁₀/T -
\(CT_{req}\) Required CT (mg·min/L) -
\(T\) Theoretical detention time s
\(t_{10}\) Effective contact time s
\(CT\) CT achieved (mg·min/L) -
\(CT/CT_{req}\) Ratio to the requirement -
\(V_{req}\) Tank volume to meet the requirement m³

Method and standards

CT concept.

Where it is used

  • Drinking water and effluent disinfection.
  • Cooling and process water.

Common mistakes

  • Using average instead of peak flow.
  • Using the dose instead of the residual.

Assumptions and limits

  • Steady flow; residual at the outlet.

References

  • US EPA
  • Disinfection Profiling and Benchmarking Guidance Manual (EPA 815-R-99-013): CT = C × t₁₀ and baffling factors

Questions and answers

What is t₁₀?

The time by which 10 % of the water has passed through the tank; short-circuiting makes it shorter than V/Q.

Why use the outlet residual?

It is the lowest concentration in the tank, so CT is conservative.

What do the defaults give?

1 mg/L in 400 m³ at 10,000 m³/d, BF 0.5: t₁₀ about 29 min, CT 29: just short of 30.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.