FireCADCalc

Primary Clarifier Sizing, Scour Velocity and BOD and TSS Removal

Rectangular primary clarifier area, length, detention and overflow rate at average and peak flow, Camp's scour velocity and BOD and TSS removal from t/(a + bt).

Refinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Small plant 4,000 m3/d, one tankLarge plant 150,000 m3/d, 8 tanks

Accepted: 8.64 to 4,320,000 m³/d
Accepted: 8.64 to 8,640,000 m³/d
Accepted: 0.864 to 86.4 m/d
Accepted: 1 to 20
Accepted: 1 to 30 m
Accepted: 1 to 8 m
Accepted: 0.01 to 0.2
Accepted: 1.01 to 3
Accepted: 0.001 to 1 mm
Accepted: 0.005 to 0.1

Results

Removal constants at 20 °C: BOD a = 0.018 h, b = 0.020; TSS a = 0.0075 h, b = 0.014 (Crites and Tchobanoglous). The typical overflow rates are 30-50 m³/m²·d at average and 80-120 at peak flow.

Required surface area (all tanks)114.29m²
Tank length28.571m
Detention at average flow2.4000h
Detention at peak flow0.96000h
Overflow rate at peak flow87.500m/d
Scour velocity0.051138m/s
Horizontal velocity at peak flow0.008267m/s
BOD removal at average flow36.364%
TSS removal at average flow58.394%
BOD removal at peak flow25.806%
TSS removal at peak flow45.845%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Small plant 4,000 m3/d, one tank. The inputs, in the units selected above:

InputValue
Average flow4,000.0 m³/d
Peak flow10,000 m³/d
Overflow rate at average flow35.000 m/d
Number of tanks1.0000 -
Tank width4.0000 m
Side water depth3.5000 m
Cohesion constant (0.04 sand, 0.06 sticky)0.050000 -
Particle specific gravity1.2000 -
Particle diameter0.10000 mm
Darcy friction factor0.030000 -

Applying the formula below gives:

ResultValue
Required surface area (all tanks)114.29 m²
Tank length28.571 m
Detention at average flow2.4000 h
Detention at peak flow0.96000 h
Overflow rate at peak flow87.500 m/d
Scour velocity0.051138 m/s
Horizontal velocity at peak flow0.008267 m/s
BOD removal at average flow36.364 %
TSS removal at average flow58.394 %
BOD removal at peak flow25.806 %
TSS removal at peak flow45.845 %

Open this example in the calculator and change any input.

Formula

\(A = \frac{Q_{avg}}{OR}, \quad t = \frac{Ah}{Q}, \quad v_H = \left[\frac{8k(s - 1)gd}{f}\right]^{1/2}, \quad R = \frac{t}{a + bt}\)

Variables

Symbol Meaning SI unit
\(Q_{avg}\) Average flow m³/s
\(Q_{peak}\) Peak flow m³/s
\(OR\) Overflow rate at average flow m/s
\(n\) Number of tanks -
\(W\) Tank width m
\(h\) Side water depth m
\(k\) Cohesion constant (0.04 sand, 0.06 sticky) -
\(s\) Particle specific gravity -
\(d\) Particle diameter m
\(f\) Darcy friction factor -
\(A\) Required surface area (all tanks) m²
\(L\) Tank length m
\(t_{avg}\) Detention at average flow s
\(t_{peak}\) Detention at peak flow s
\(OR_p\) Overflow rate at peak flow m/s
\(v_H\) Scour velocity m/s
\(v_p\) Horizontal velocity at peak flow m/s
\(R_{BOD}\) BOD removal at average flow -
\(R_{TSS}\) TSS removal at average flow -
\(R_{BOD,p}\) BOD removal at peak flow -
\(R_{TSS,p}\) TSS removal at peak flow -

Method and standards

Primary sedimentation design.

Where it is used

  • Primary clarifier sizing.
  • Estimating loads to secondary treatment.

Common mistakes

  • Entering the detention time in minutes in t/(a + bt), whose constants are for hours.
  • Using one tank's width with the total area.

Assumptions and limits

  • Empirical removal curves at 20 °C for typical municipal wastewater.

Questions and answers

What does the scour check tell me?

If the horizontal velocity along the tank approached Camp's scour velocity, settled sludge would be picked up again; it is normally an order of magnitude lower.

What do the defaults represent?

An illustrative case: Small plant 4,000 m3/d, one tank. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 5-6, eqs. 5-45 and 5-46 and Example 5-9 (Crites and Tchobanoglous 1998; Camp 1946)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.