Area of sludge drying beds from the daily sludge volume, the drying cycle and the depth of sludge applied, and the number of beds of a given size.

Inputs

Examples: Illustrative 2 m3/day STP sludgeSmall ETP, 0.5 m3/dayMonsoon cycle, 5 m3/day

Accepted: 0.000864 to 86,400 m³/d
Accepted: 1 to 115.74 d
Accepted: 50 to 1,000 mm
Accepted: 1 to 1,000 m²

Results

Each bed is filled, drains and dries for a cycle of one to four weeks depending on climate, so the beds must hold all the sludge produced during one cycle at the chosen depth (20–30 cm). Dividing by the area of one bed gives the number of beds, which also lets one be filled each day or few days. Allow extra area for the monsoon, or cover the beds.

Sludge applied per cycle30.000m³
Total bed area120.00m²
Number of beds3.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 2 m3/day STP sludge. The inputs, in the units selected above:

InputValue
Wet sludge volume to dry per day2.0000 m³/d
Drying cycle (fill to removal)15.000 d
Depth of sludge applied250.00 mm
Area of one bed40.000 m²

Applying the formula below gives:

ResultValue
Sludge applied per cycle30.000 m³
Total bed area120.00 m²
Number of beds3.0000

Open this example in the calculator and change any input.

Formula

\(V_c = \dot V_s t_c, \quad A = \frac{V_c}{d}, \quad n = \left\lceil\frac{A}{A_b}\right\rceil\)

Variables

Symbol Meaning SI unit
\(\dot V_s\) Wet sludge volume to dry per day m³/s
\(t_c\) Drying cycle (fill to removal) s
\(d\) Depth of sludge applied m
\(A_b\) Area of one bed m²
\(V_c\) Sludge applied per cycle m³
\(A\) Total bed area m²
\(n\) Number of beds -

Method and standards

Drying beds.

Where it is used

  • Small STPs and ETPs.
  • Water treatment plant sludge.

Common mistakes

  • Ignoring rainy-season cycles.
  • Applying sludge too deep.

Assumptions and limits

  • Uniform sludge production.

References

  • Volume-per-cycle sizing of sludge drying beds

Questions and answers

How much drying bed for 2 m³/day of sludge?

With a 15-day cycle at 25 cm, 120 m², or three 40 m² beds.

Why size on the cycle?

Each bed is out of use for the whole cycle while its sludge dries.

What do the defaults represent?

An illustrative STP producing 2 m³/day of wet sludge, 15-day cycle, 25 cm depth, 40 m² beds.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.