FireCADCalc

Gravity Thickener for Combined Primary and Waste Activated Sludge

Dry solids of two sludge streams, combined flow and concentration, thickener area from the solids loading, hydraulic loading and diameter of each unit.

Refinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Primary sludge only, 120 kg/m2.d

Accepted: 0 to 864,000 m³/d
Accepted: 1 to 1.3
Accepted: 0 to 20 %
Accepted: 0 to 864,000 m³/d
Accepted: 1 to 1.3
Accepted: 0 to 20 %
Accepted: 1 to 1.3
Accepted: 0.864 to 864 kg/(m²·d)
Accepted: 1 to 10

Results

The solids loadings: primary sludge 100-150 kg/m²·d, waste activated alone 20-40, primary plus WAS at 0.5-1.5 % solids 25-70. Hydraulic loadings below about 15-30 m³/m²·d risk septic, odorous conditions; add dilution water if needed. Units over 20 m diameter are unusual.

Primary dry solids6,120.0kg/d
WAS dry solids0kg/d
Combined dry solids6,120.0kg/d
Combined flow150.00m³/d
Combined solids4.0000%
Total area51.000m²
Hydraulic loading2.9412m/d
Diameter of each thickener8.0582m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Primary sludge only, 120 kg/m2.d. The inputs, in the units selected above:

InputValue
Primary sludge flow150.00 m³/d
Primary sludge specific gravity1.0200 -
Primary sludge solids4.0000 %
Waste activated sludge flow0 m³/d
WAS specific gravity1.0000 -
WAS solids0 %
Combined sludge specific gravity1.0200 -
Solids loading120.00 kg/(m²·d)
Number of thickeners1.0000 -

Applying the formula below gives:

ResultValue
Primary dry solids6,120.0 kg/d
WAS dry solids0 kg/d
Combined dry solids6,120.0 kg/d
Combined flow150.00 m³/d
Combined solids4.0000 %
Total area51.000 m²
Hydraulic loading2.9412 m/d
Diameter of each thickener8.0582 m

Open this example in the calculator and change any input.

Formula

\(M_i = Q_i\,SG_i\,\rho_w\,P_i, \quad P = \frac{M_1 + M_2}{(Q_1 + Q_2)SG_m\rho_w}, \quad A = \frac{M}{SL}, \quad D = \sqrt{\frac{4A}{n\pi}}\)

Variables

Symbol Meaning SI unit
\(Q_1\) Primary sludge flow m³/s
\(SG_1\) Primary sludge specific gravity -
\(P_1\) Primary sludge solids -
\(Q_2\) Waste activated sludge flow m³/s
\(SG_2\) WAS specific gravity -
\(P_2\) WAS solids -
\(SG_m\) Combined sludge specific gravity -
\(SL\) Solids loading kg/(m²·s)
\(n\) Number of thickeners -
\(M_1\) Primary dry solids kg/s
\(M_2\) WAS dry solids kg/s
\(M\) Combined dry solids kg/s
\(Q\) Combined flow m³/s
\(P\) Combined solids -
\(A\) Total area m²
\(HL\) Hydraulic loading m/s
\(D\) Diameter of each thickener m

Method and standards

Solids-loading design of gravity thickeners.

Where it is used

  • Sludge thickener sizing.
  • Checking thickener loading in operation.

Common mistakes

  • Designing on average instead of peak solids.
  • Mixing percent and fraction.

Assumptions and limits

  • Typical-value design; settling tests are better.

Questions and answers

Why check the hydraulic loading?

A gravity thickener sized on solids alone may see so little flow that sludge goes septic; dilution water or effluent recycle raises the overflow.

Should WAS go to a gravity thickener?

Waste activated sludge thickens poorly by gravity; flotation, centrifuges or gravity belts are often used for it, with the primary sludge thickened separately.

What do the defaults represent?

An illustrative case: Primary sludge only, 120 kg/m2.d. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 13-6, Table 13-19 and Example 13-4

Related calculators