Worked example
Example: Small plant 300 kg/d at 2 %, 40 d. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Waste sludge to the digester (dry) | 300.00 kg/d |
| Thickened sludge solids | 2.0000 % |
| Sludge specific gravity | 1.0200 - |
| Solids retention time | 40.000 d |
| Volatile fraction of the sludge | 75.000 % |
| Volatile solids reduction (from degree-days) | 40.000 % |
| Oxygen per VSS destroyed | 2.3000 kg/kg |
| Air density at standard conditions | 1.2040 kg/m³ |
| Oxygen transfer efficiency | 8.0000 % |
| Liquid temperature (for degree-days) | 20.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sludge flow | 14.706 m³/d |
| Digester volume | 588.24 m³ |
| VSS destroyed | 90.000 kg/d |
| Oxygen required | 207.00 kg/d |
| Air at standard conditions | 741.06 m³/d |
| Air supplied | 6.4328 m³/min |
| Air per digester volume | 0.010936 1/min |
| Degree-days | 800.00 |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{M}{\rho_wSG\,P_s}, \quad V = Q\cdot SRT, \quad O_2 = 2.3\,f_vR_{VS}M, \quad V_{air} = \frac{O_2}{0.232\rho_a}, \quad q = \frac{V_{air}}{OTE}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(M\) | Waste sludge to the digester (dry) | kg/s |
| \(P_s\) | Thickened sludge solids | - |
| \(SG\) | Sludge specific gravity | - |
| \(SRT\) | Solids retention time | s |
| \(f_v\) | Volatile fraction of the sludge | - |
| \(R_{VS}\) | Volatile solids reduction (from degree-days) | - |
| \(r_{O_2}\) | Oxygen per VSS destroyed | kg/kg |
| \(\rho_a\) | Air density at standard conditions | kg/m³ |
| \(OTE\) | Oxygen transfer efficiency | - |
| \(T\) | Liquid temperature (for degree-days) | K |
| \(Q\) | Sludge flow | m³/s |
| \(V\) | Digester volume | m³ |
| \(VSS_{red}\) | VSS destroyed | kg/s |
| \(O_2\) | Oxygen required | kg/s |
| \(V_{air}\) | Air at standard conditions | m³/s |
| \(q_{air}\) | Air supplied | m³/s |
| \(q_{air}/V\) | Air per digester volume | 1/s |
| \(T\cdot SRT\) | Degree-days | - |
Method and standards
Aerobic digester design.
Where it is used
- Aerobic digestion for small plants.
- Blower sizing for digesters.
Common mistakes
- Ignoring mixing.
- Using the summer VSR for the winter volume.
Assumptions and limits
- Single-stage complete mix; nitrification complete.
Questions and answers
Where does 2.3 kg O₂ per kg VSS come from?
Endogenous oxidation of cell mass (C₅H₇NO₂) to CO₂, water and nitrate needs about 2.3 kg of oxygen per kilogram of cells destroyed when nitrification is complete.
What do the defaults represent?
An illustrative case: Small plant 300 kg/d at 2 %, 40 d. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 13-10, Example 13-8 and Tables 13-44 and 13-45