Worked example
Example: Same bed in winter water at 5 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Backwash rate | 0.75000 m/min |
| Bed depth | 0.90000 m |
| Bed porosity (fixed) | 40.000 % |
| Media specific gravity | 2.6500 - |
| Water temperature | 5.0000 °C |
| Size of fraction 1 | 2.1800 mm |
| Mass fraction 1 | 1.0000 % |
| Size of fraction 2 | 1.8300 mm |
| Mass fraction 2 | 3.0000 % |
| Size of fraction 3 | 1.3000 mm |
| Mass fraction 3 | 16.000 % |
| Size of fraction 4 | 0.92000 mm |
| Mass fraction 4 | 16.000 % |
| Size of fraction 5 | 0.71000 mm |
| Mass fraction 5 | 30.000 % |
| Size of fraction 6 | 0.50000 mm |
| Mass fraction 6 | 22.000 % |
| Size of fraction 7 | 0.35000 mm |
| Mass fraction 7 | 12.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Expanded bed depth | 1.4858 m |
| Bed expansion | 65.090 % |
| Expanded porosity of the coarsest fraction | 0.49906 |
| Settling velocity of the coarsest fraction | 0.29439 m/s |
| Settling velocity of the finest fraction | 0.046469 m/s |
Open this example in the calculator and change any input.
Formula
\(\frac{L_e}{L} = (1 - \alpha)\sum\frac{p_i}{1 - \alpha_{e,i}}, \quad \alpha_{e,i} = \left(\frac{v}{v_{s,i}}\right)^{0.22}, \quad C_d = \frac{24}{Re} + \frac{3}{\sqrt{Re}} + 0.34\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(v\) | Backwash rate | m/s |
| \(L\) | Bed depth | m |
| \(\alpha\) | Bed porosity (fixed) | - |
| \(s\) | Media specific gravity | - |
| \(T\) | Water temperature | K |
| \(d_1\) | Size of fraction 1 | m |
| \(p_1\) | Mass fraction 1 | - |
| \(d_2\) | Size of fraction 2 | m |
| \(p_2\) | Mass fraction 2 | - |
| \(d_3\) | Size of fraction 3 | m |
| \(p_3\) | Mass fraction 3 | - |
| \(d_4\) | Size of fraction 4 | m |
| \(p_4\) | Mass fraction 4 | - |
| \(d_5\) | Size of fraction 5 | m |
| \(p_5\) | Mass fraction 5 | - |
| \(d_6\) | Size of fraction 6 | m |
| \(p_6\) | Mass fraction 6 | - |
| \(d_7\) | Size of fraction 7 | m |
| \(p_7\) | Mass fraction 7 | - |
| \(L_e\) | Expanded bed depth | m |
| \((L_e - L)/L\) | Bed expansion | - |
| \(\alpha_{e,1}\) | Expanded porosity of the coarsest fraction | - |
| \(v_{s,1}\) | Settling velocity of the coarsest fraction | m/s |
| \(v_{s,7}\) | Settling velocity of the finest fraction | m/s |
Method and standards
Fair and Geyer expansion with the Richardson-Zaki type porosity relation.
Where it is used
- Setting backwash rates and trough heights.
- Checking seasonal temperature effects on backwash.
Common mistakes
- Using the effective size for the whole bed.
- Ignoring temperature: cold water expands the bed more.
Assumptions and limits
- Spherical-particle drag law; sieve geometric mean sizes.
Questions and answers
How much expansion is wanted?
Typically 30-50 %; the bottom of the wash troughs is set 50-150 mm above the expanded bed.
Why must the coarsest fraction expand?
If its expanded porosity stays below the fixed-bed porosity, the coarse grains at the bottom are not fluidised and the bed will not be cleaned throughout.
What do the defaults represent?
An illustrative case: Same bed in winter water at 5 C. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 11-4, eq. 11-19 and Example 11-2; drag law eq. 5-10