Worked example
Example: Same resin with 1.25 design factor. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Throughput at C/C₀ = 0.5 for the first ion (e.g. Cl⁻) | 7.5000 L |
| Throughput at C/C₀ = 0.5 for the exchanged ion (e.g. Ca²⁺) | 22.100 L |
| Feed concentration of the exchanged ion (meq/L) | 2.0000 - |
| Resin mass in the test | 0.10000 kg |
| Water to treat | 4,000.0 m³ |
| Ion to remove (meq/L) | 1.0000 - |
| Resin bulk density | 700.00 kg/m³ |
| Design factor for leakage (1.1-1.4) | 1.2500 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Exchange capacity (meq/kg) | 292.00 |
| Equivalents to remove (eq) | 4,000.0 |
| Resin mass | 17,123 kg |
| Resin volume | 24.462 m³ |
| Capacity as g CaCO₃ per m³ of resin | 10,220 g/m³ |
Open this example in the calculator and change any input.
Formula
\(EC = \frac{(V_2 - V_1)C_o}{R}, \quad R_{mass} = f\frac{C_tV_t}{EC}, \quad R_{vol} = \frac{R_{mass}}{\rho_r}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_1\) | Throughput at C/C₀ = 0.5 for the first ion (e.g. Cl⁻) | m³ |
| \(V_2\) | Throughput at C/C₀ = 0.5 for the exchanged ion (e.g. Ca²⁺) | m³ |
| \(C_o\) | Feed concentration of the exchanged ion (meq/L) | - |
| \(R\) | Resin mass in the test | kg |
| \(V_t\) | Water to treat | m³ |
| \(C_t\) | Ion to remove (meq/L) | - |
| \(\rho_r\) | Resin bulk density | kg/m³ |
| \(f\) | Design factor for leakage (1.1-1.4) | - |
| \(EC\) | Exchange capacity (meq/kg) | - |
| \(N\) | Equivalents to remove (eq) | - |
| \(R_{mass}\) | Resin mass | kg |
| \(R_{vol}\) | Resin volume | m³ |
| \(EC_v\) | Capacity as g CaCO₃ per m³ of resin | kg/m³ |
Method and standards
Column test exchange capacity and bed sizing.
Where it is used
- Ion exchange design for ammonium, hardness or nitrate.
- Comparing resins.
Common mistakes
- Entering mg/L instead of meq/L.
- Using total throughput instead of the difference.
Assumptions and limits
- Full use of capacity at the half-breakthrough points.
Questions and answers
Why use the difference of two breakthrough volumes?
The first ion (chloride, displaced from the void volume) marks the hydraulic hold-up; the exchanged ion breaks through only after the resin sites are full, so the difference is the volume whose ions were taken up.
Is the resin fully used in service?
No: a column is taken off line at a leakage limit before the bed is exhausted, hence the 1.1-1.4 factor.
What do the defaults represent?
An illustrative case: Same resin with 1.25 design factor. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.