Worked example
Example: Brackish RO: 20 m³/h feed, 15 m³/h permeate, 1500 mg/L, 98 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Feed flow | 20.000 m³/h |
| Permeate flow | 15.000 m³/h |
| Feed TDS | 1,500.0 mg/L |
| Salt rejection | 98.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Recovery | 75.000 % |
| Reject flow | 5.0000 m³/h |
| Permeate TDS | 30.000 mg/L |
| Reject TDS | 5,910.0 mg/L |
| Concentration factor of the reject | 3.9400 |
Open this example in the calculator and change any input.
Formula
\(r = \frac{Q_p}{Q_f} \qquad Q_r = Q_f - Q_p \qquad C_p = (1 - R)\,C_f \qquad C_r = \frac{Q_f\,C_f - Q_p\,C_p}{Q_r} \qquad CF = \frac{C_r}{C_f}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_f\) | feed flow | m³/s |
| \(Q_p\) | permeate flow | m³/s |
| \(C_f\) | feed TDS | kg/m³ |
| \(R\) | salt rejection | – |
| \(r\) | recovery | – |
| \(Q_r\) | reject flow | m³/s |
| \(C_p\) | permeate TDS | kg/m³ |
| \(C_r\) | reject TDS | kg/m³ |
| \(CF\) | concentration factor | – |
Method and standards
Water and salt balances across the RO; permeate TDS from the salt rejection on the feed concentration (a simple, slightly optimistic basis; membrane software uses the average feed-concentrate concentration).
Where it is used
- First sizing of RO plants for boiler make-up.
- Disposal planning for the reject stream.
- Monitoring recovery and salt passage.
Common mistakes
- Taking the rejection on the feed when the membrane data quote it on the average concentration.
- Forgetting the reject volume in the raw water demand.
- Pushing recovery without checking scaling.
Assumptions and limits
- Steady state; rejection constant; no concentration polarisation.
- At high recovery the permeate TDS on the feed basis can be several times too low; the note gives the value on the average feed-reject concentration.
- The 85 % recovery warning is a screening level, not a sourced limit.
References
- Reverse-osmosis mass balance (water and salt)
Questions and answers
What is RO recovery?
Permeate flow over feed flow. 15 m³/h of permeate from 20 m³/h of feed is 75 % recovery, leaving 5 m³/h of reject.
How salty is the reject?
With 1500 mg/L feed and 98 % rejection, the permeate has 30 mg/L and the reject 5910 mg/L, a concentration factor of 3.9.
Why not run at higher recovery?
The reject concentrates and scales the last membranes. The membrane maker's design software sets the safe recovery for your water and antiscalant.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.