Worked example
Example: 80 m3, three fills. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam–water volume to fill | 80.000 m³ |
| Nitrogen capping pressure (absolute) | 1.5000 bar |
| Temperature | 30.000 °C |
| Fills (including purges) | 3.0000 - |
| Nitrogen per cylinder (normal m³) | 7.0000 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Nitrogen (normal m³ at 0 °C, 1 atm) | 320.13 m³ |
| Cylinders | 46.000 |
Open this example in the calculator and change any input.
Formula
\(V_n = V \frac{p}{p_n}\frac{T_n}{T} n\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Steam–water volume to fill | m³ |
| \(p\) | Nitrogen capping pressure (absolute) | Pa |
| \(T\) | Temperature | K |
| \(n\) | Fills (including purges) | - |
| \(V_c\) | Nitrogen per cylinder (normal m³) | m³ |
| \(V_n\) | Nitrogen (normal m³ at 0 °C, 1 atm) | m³ |
| \(N_c\) | Cylinders | - |
Method and standards
Ideal gas.
Where it is used
- Off-season preservation.
- Long outages.
Common mistakes
- Gauge pressure used as absolute.
Assumptions and limits
- Ideal gas.
- Each fill or purge counts as a full boiler volume of nitrogen at the absolute capping pressure (displacement purging). Pressure purges vented to atmosphere use only about V(p − p_atm)/p_n per cycle, so the result is conservative for them (about 3 times high at 1.5 bar absolute).
- Volumes are normal cubic metres at 0 °C and 1 atm, shown in m³ in every unit system; US standard cubic feet at 60 °F are a different basis.
References
- Ideal gas V_n = V (p/p_n)(T_n/T) n
Questions and answers
When to lay up with nitrogen?
For off-season sugar and distillery boilers standing for weeks or months.
Wet or dry lay-up?
Wet lay-up with chemicals for short stops; dry with nitrogen or desiccant for long ones.
Why several fills?
Purging displaces air step by step before the final capping fill.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.