Worked example
Example: Bi-drum 50 t/h: drum 1.5 m x 9 m, water 0.75 m; 600 tubes 57 mm ID x 12 m; 8 headers 250 mm x 6 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Working pressure (absolute) | 66.000 bar |
| Drum inside diameter | 1.5000 m |
| Drum length | 9.0000 m |
| Water level above the drum bottom | 0.75000 m |
| Number of tubes | 600.00 - |
| Tube inside diameter | 57.000 mm |
| Mean tube length | 12.000 m |
| Number of headers | 8.0000 - |
| Header inside diameter | 250.00 mm |
| Header length | 6.0000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total water volume | 28.681 m³ |
| Water mass at working pressure (all tubes full of saturated water) | 21.423 t |
| Water in the drum | 7.9522 m³ |
| Water in the tubes | 18.373 m³ |
| Water in the headers | 2.3562 m³ |
Open this example in the calculator and change any input.
Formula
\(V_d = L_d\left[R^2\cos^{-1}\frac{R - h}{R} - (R - h)\sqrt{2Rh - h^2}\right] \qquad V_t = n_t\frac{\pi d_t^2}{4} l_t \qquad V_h = n_h\frac{\pi d_h^2}{4} l_h \qquad M_w = \rho_f\,V\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | working pressure | Pa |
| \(D\) | drum inside diameter | m |
| \(R\) | drum radius, D/2 | m |
| \(L_d\) | drum length | m |
| \(h\) | water level above drum bottom | m |
| \(n_t\) | tubes | – |
| \(d_t\) | tube bore | m |
| \(l_t\) | tube length | m |
| \(n_h\) | headers | – |
| \(d_h\) | header bore | m |
| \(l_h\) | header length | m |
| \(V\) | total water volume | m³ |
| \(M_w\) | water mass | kg |
| \(V_d\) | drum water | m³ |
| \(V_t\) | tube water | m³ |
| \(V_h\) | header water | m³ |
| \(\rho_f\) | saturated water density (IF97) | kg/m³ |
Method and standards
Circular segment for the drum, full cylinders for tubes and headers; saturated water density from FireCAD's IAPWS-IF97.
Where it is used
- Chemical cleaning and boil-out quantities.
- Start-up and flash calculations.
- Support and foundation loads.
Common mistakes
- Forgetting downcomers, economiser and lower drum.
- Using cold density at working pressure.
- Ignoring the steam bubbles in risers, which reduce the water mass in operation.
Assumptions and limits
- Drum without dished ends; tubes and headers full of saturated water. In operation the risers carry steam, so the operating water mass is lower than shown; the figure is the flooded-to-level content.
References
- Circular segment geometry
- IAPWS R7-97 IF97
Questions and answers
How much water is in a boiler?
A bi-drum boiler with a 1.5 × 9 m drum half full, 600 tubes of 57 mm bore and 12 m length, and eight 250 mm headers holds 28.7 m³: 21.4 t at 66 bar(a).
Why do I need it?
For chemical cleaning and dosing, start-up heat, flash on pressure drop, and the weight on the supports.
Is the water mass the same cold?
No: cold water is denser, so a flooded boiler for a hydraulic test holds more mass than this.