Worked example
Example: Shell boiler: 12 t water, 25 t steel, cold 30 °C to 10.5 bar(a), 2 MW firing at 60 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water in the boiler | 12.000 t |
| Pressure-part steel heated with the water | 25.000 t |
| Mean specific heat of the steel | 0.48000 kJ/(kg·K) |
| Starting temperature (water and steel) | 30.000 °C |
| Working pressure (absolute) | 10.500 bar |
| Start-up firing rate (fuel heat input) | 2,000.0 kW |
| Share of the firing heat that reaches water and steel | 60.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Time to reach working pressure | 2.2151 h |
| Average heating rate | 68.629 °C/h |
| Heat needed | 9.5691 GJ |
| Of which to the water | 7.7449 GJ |
| Of which to the steel | 1.8242 GJ |
| Saturation temperature at working pressure | 182.02 °C |
Open this example in the calculator and change any input.
Formula
\(Q_w = M_w\,\left[h_f(p) - h(p, T_0)\right] \qquad Q_m = M_m\,c_m\,(T_{sat} - T_0) \qquad Q = Q_w + Q_m\)
\(t = \frac{Q}{\eta_s\,\dot Q_f} \qquad \dot T = \frac{T_{sat} - T_0}{t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(M_w\) | water in the boiler | kg |
| \(M_m\) | steel heated with the water | kg |
| \(c_m\) | mean specific heat of the steel | J/(kg·K) |
| \(T_0\) | starting temperature | K |
| \(p\) | working pressure, absolute | Pa |
| \(\dot Q_f\) | start-up firing rate | W |
| \(\eta_s\) | share of firing heat reaching water and steel | – |
| \(t\) | time to working pressure | s |
| \(\dot T\) | average heating rate | K/s |
| \(Q\) | heat needed | J |
| \(Q_w\) | heat to the water | J |
| \(Q_m\) | heat to the steel | J |
| \(T_{sat}\) | saturation temperature at working pressure | K |
| \(h_f\), \(h\) | water enthalpies (IF97) | J/kg |
Method and standards
Energy balance of the water and steel from the starting temperature to saturation at working pressure; water enthalpies from FireCAD's IAPWS-IF97. Steam vented during start-up and refractory heat are not included.
Where it is used
- Planning start-up times and fuel.
- Comparing cold, warm and hot starts.
- Checking firing rate against the maker's heating curve.
Common mistakes
- Forgetting the steel and refractory, which can need as much heat as the water.
- Taking the start-up efficiency equal to full-load efficiency.
- Firing faster than the allowed temperature rise.
Assumptions and limits
- Water mass constant; uniform temperature of water and steel; no venting or refractory heat.
- The heating rate is an average from \(T_0\) to \(T_{sat}\). The saturation temperature does not rise linearly in time, and the boiler maker's limit applies to the instantaneous rate, which can be higher than the average.
References
- IAPWS R7-97(2012) IF97
- first law of thermodynamics
Questions and answers
How long does a boiler take to start from cold?
Heat needed divided by the useful firing rate. A shell boiler with 12 t of water and 25 t of steel from 30 °C to 10.5 bar(a) needs 9.6 GJ; at 2 MW firing with 60 % reaching the boiler that is 2.2 hours, an average rise of 69 °C/h.
Why not fire harder?
Thick drums, shells and headers heat from the inside; fast heating causes thermal stress and cracking at tube holes. The boiler maker's start-up curve sets the allowed rate.
How much does a warm start save?
Starting at 90 °C instead of 30 °C saves the heat for that 60 K of water and steel: about 40 % of the cold-start heat in this example (5.8 GJ instead of 9.6 GJ).
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.