Worked example
Example: 25 MW boiler, 1000 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Full-load heat input | 25.000 MW |
| Standing loss (share of full-load input) | 3.0000 % |
| Hours banked | 1,000.0 h |
| Fuel GCV | 23,000 kJ/kg |
| Fuel price per tonne | 9,000.0 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy lost | 2,700.0 GJ |
| Fuel burnt | 117.39 t |
| Cost | 1,056,522 |
Open this example in the calculator and change any input.
Formula
\(E = \dot Q_{100}\,l\,t, \quad M = \frac{E}{GCV}, \quad C = \frac{M}{1000\ \text{kg/t}}\,c\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q_{100}\) | Full-load heat input | W |
| \(l\) | Standing loss (share of full-load input) | - |
| \(t\) | Hours banked | s |
| \(GCV\) | Fuel GCV | J/kg |
| \(c\) | Fuel price per tonne | - |
| \(E\) | Energy lost | J |
| \(M\) | Fuel burnt | kg |
| \(C\) | Cost | - |
Method and standards
Definitions. The standing loss has no general published value; measure it as the fuel burnt over a banked period divided by the full-load fuel rate.
Where it is used
- Standby policy.
- Energy audits.
Common mistakes
- Standing loss as share of output.
Assumptions and limits
- Constant loss. The input is capped at 20 % of full-load input as a plausibility limit; real standing losses are a few per cent with dampers closed.
References
- Energy balance definitions; standing loss from a site measurement of fuel burnt while banked
Questions and answers
Bank or shut down?
Compare banking fuel with start-up fuel and the risk of a slow restart.
Typical standing loss?
A few per cent of full-load input with dampers closed.
Why close dampers?
Natural draught pulls cold air through a hot boiler.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.