Worked example
Example: Natural gas. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Methane (CH4) | 95.000 % |
| Ethane (C2H6) | 2.5000 % |
| Propane (C3H8) | 0.20000 % |
| Butane (C4H10) | 0 % |
| Pentane (C5H12) | 0 % |
| Ethylene (C2H4) | 0 % |
| Propylene (C3H6) | 0 % |
| Benzene (C6H6) | 0 % |
| Hydrogen (H2) | 0 % |
| Carbon monoxide (CO) | 0 % |
| Hydrogen sulphide (H2S) | 0 % |
| Water vapour (H2O) | 0 % |
| Carbon dioxide (CO2) | 0.60000 % |
| Nitrogen (N2) | 1.7000 % |
| Oxygen (O2) | 0 % |
| Sulphur dioxide (SO2) | 0 % |
| Excess air | 10.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Combustion air temperature entering the boiler | 30.000 °C |
| Flue gas temperature leaving the boiler (after air heater) | 120.00 °C |
| CO in dry flue gas | 20.000 ppm |
| Surface radiation and convection loss | 1.0000 % |
| Unaccounted loss / manufacturer's margin | 0.50000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Gross calorific value per Nm³ | 39,686 kJ/Nm³ |
| Gross calorific value used | 52,882 kJ/kg |
| Net calorific value | 47,696 kJ/kg |
| Dry gas loss | 3.0666 % |
| Water from hydrogen in fuel | 10.526 % |
| Moisture in fuel | 0 % |
| Moisture in air | 0.079287 % |
| Unburned CO | 0.014168 % |
| Surface radiation and convection | 1.0000 % |
| Unaccounted | 0.50000 % |
| Total losses | 15.186 % |
| Credit: entering dry air above 25 °C | 0.17160 % |
| Credit: moisture in entering air | 0.004140 % |
| Total credits | 0.17574 % |
| Fuel efficiency, gross (HHV) basis | 84.989 % |
| Efficiency, net (LHV) basis | 94.230 % |
Open this example in the calculator and change any input.
Formula
Losses per kg fuel gas, divided by the gross calorific value:
\(L_{dg} = m_{g,dry}\left[h_{g}(T_g) - h_{g}(T_{ref})\right] \qquad L_{H} = m_{H_2O,H}\left[h_v(T_g) - h_f(T_{ref})\right] \qquad L_{M} = m_{H_2O,f}\left[h_v(T_g) - h_f(T_{ref})\right]\)
\(L_{\omega} = \omega\,m_a\left[h_v(T_g) - h_v(T_{ref})\right] \qquad L_{CO} = y_{CO}\,\frac{m_{g,dry}}{M_{g,dry}}\,M_{CO}\,\Delta h_{CO}\)
\(B_{a} = m_a\left[h_{air}(T_a) - h_{air}(T_{ref})\right] \qquad B_{\omega} = \omega\,m_a\left[h_v(T_a) - h_v(T_{ref})\right] \qquad \eta_{GCV} = 1 - \frac{\sum L}{GCV} + \frac{\sum B}{GCV} \qquad \eta_{NCV} = \eta_{GCV}\,\frac{GCV}{NCV}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(y_{CH_4}\), \(y_{C_2H_6}\), \(y_{C_3H_8}\), \(y_{C_4H_{10}}\), \(y_{C_5H_{12}}\), \(y_{C_2H_4}\), \(y_{C_3H_6}\), \(y_{C_6H_6}\), \(y_{H_2}\), \(y_{CO}\), \(y_{H_2S}\), \(y_{H_2O}\), \(y_{CO_2}\), \(y_{N_2}\), \(y_{O_2}\), \(y_{SO_2}\) | fuel gas analysis by volume; \(y_{CO}\) also names the CO reading in dry flue gas under operating data | – |
| \(EA\) | excess air fraction | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(T_a\), \(T_g\) | entering air and leaving flue gas temperatures | K |
| \(T_{ref}\) | reference temperature, 298.15 K | K |
| \(m_a\), \(m_{g,dry}\) | actual dry air and dry flue gas per kg fuel | kg/kg |
| \(m_{H_2O,H}\), \(m_{H_2O,f}\) | water formed from hydrogen and water vapour carried in the fuel gas, per kg fuel | kg/kg |
| \(M_{g,dry}\), \(M_{CO}\) | molar mass of dry flue gas and of CO | kg/kmol |
| \(h_g\), \(h_{air}\), \(h_v\), \(h_f\) | enthalpies of dry flue gas, air, water vapour and liquid water at 25 °C; \(h_v\) is IF97 at 1 psia for water from the fuel and ideal-gas (Shomate) H₂O for the moisture in air | J/kg |
| \(\Delta h_{CO}\) | heat of burning CO to CO₂, 23.63 MJ/kg | J/kg |
| \(GCV_v\) | gross calorific value per normal cubic metre | J/Nm³ |
| \(GCV\), \(NCV\) | gross and net calorific value per kg | J/kg |
| \(L_{dg}\), \(L_{H}\), \(L_{M}\), \(L_{\omega}\), \(L_{CO}\), \(L_{rc}\), \(L_{un}\) | losses: dry gas, water from hydrogen, fuel moisture, air moisture, CO, radiation and convection, unaccounted | – |
| \(\sum L\), \(\sum B\), \(B_{a}\), \(B_{\omega}\) | total losses, total credits, dry air credit, air moisture credit | – |
| \(\eta_{GCV}\), \(\eta_{NCV}\) | efficiency on the gross and the net basis | – |
Method and standards
ASME PTC 4-2013 energy balance method (owner decision 2026-11-09) applied to the mass-basis combustion balance of the gaseous combustion calculator. The heating value is built from the standard molar heats of combustion of the species (NIST) so that fuel, air and losses are consistent; gas enthalpies are integrated from Shomate heat capacities of the actual flue gas; water vapour from the fuel from IF97 at 1 psia, the moisture in air (which stays vapour) from the ideal-gas Shomate H₂O enthalpy. Water vapour already in the fuel gas is charged like fuel moisture, from liquid at 25 °C.
Where it is used
- Natural gas and LPG fired shell, water-tube and package boilers in process plants.
- Burner tuning: seeing what each point of O₂ or each 10 K of stack temperature is worth.
- Comparing standard and condensing boilers on the same (GCV) basis.
Common mistakes
- Quoting efficiency on NCV and comparing it with a GCV figure: for natural gas the gap is about 10 points.
- Ignoring the water vapour from hydrogen, the largest loss of a gas boiler.
- Using a gas composition from another supply; the hydrogen-to-carbon ratio changes the loss.
Assumptions and limits
- No residue, no unburned carbon; incomplete combustion appears as CO, which replaces CO₂ in the dry gas (leaving half its oxygen) before the dry gas loss is found.
- Excess air is an input; to find it from a measured O₂ reading use the excess air from O₂ calculator.
- Flue gas temperature above about 39 °C and above the entering air temperature.
- Fuel sensible heat is not credited.
References
- ASME PTC 4-2013 Fired Steam Generators §5.14 and §5.15
- NIST Chemistry WebBook (heats of combustion)
Questions and answers
Why is a gas boiler's gross efficiency so much lower than its net efficiency?
Methane makes 2.25 kg of water per kg of fuel. Its latent heat is about 10 % of the gross calorific value and leaves with the flue gas unless the boiler condenses, so the HHV efficiency is roughly 10 points below the LHV efficiency.
Can I enter the GCV from the gas supplier instead?
This calculator derives it from the analysis, so the heating value and the stoichiometry are consistent. If the supplier's GCV differs by more than 2 %, the analysis is probably out of date; use the current one.
Why is there no unburned carbon loss?
Gaseous fuels leave no residue. Incomplete combustion shows up as CO, which is the loss entered here.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.