Worked example
Example: 2 MW, 90/70 °C, 4 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Boiler heat output | 2,000.0 kW |
| Supply (flow) temperature | 90.000 °C |
| Return temperature | 70.000 °C |
| Water pressure (absolute) | 4.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water mass flow | 85,812 kg/h |
| Water volume flow at the return temperature | 87.751 m³/h |
| Mean specific heat (enthalpy difference over ΔT) | 4.1952 kJ/(kg·K) |
| Margin of the supply below boiling | 53.613 K |
Open this example in the calculator and change any input.
Formula
\(\dot m = \frac{\dot Q}{h(T_s) - h(T_r)} \qquad \dot V = \frac{\dot m}{\rho(T_r)} \qquad \bar c_p = \frac{h(T_s) - h(T_r)}{T_s - T_r} \qquad \Delta T_{sub} = T_{sat}(p) - T_s\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | heat output | W |
| \(T_s\) | supply temperature | K |
| \(T_r\) | return temperature | K |
| \(p\) | water pressure | Pa |
| \(\dot m\) | mass flow | kg/s |
| \(\dot V\) | volume flow | m³/s |
| \(\bar c_p\) | mean specific heat | J/(kg·K) |
| \(\Delta T_{sub}\) | margin below boiling | K |
Method and standards
Energy balance with IAPWS-IF97 liquid enthalpies.
Where it is used
- Hot water and HTHW boilers.
- Process heating loops.
- District heating.
Common mistakes
- Mixing up flow and return.
- Not pressurising HTHW enough.
- Using the supply density for return-side pumps.
Assumptions and limits
- Liquid water; boiler output as heat to the water.
- One pressure is used for both enthalpies and the boiling margin; enter the lowest pressure at the hot supply (boiler outlet or pump suction).
- The 15 K warning margin is a FireCAD rule of thumb, not a code value; follow the boiler maker's or the code's required margin.
References
- IAPWS-IF97
Questions and answers
What flow does a 2 MW boiler need at 90/70 °C?
23.8 kg/s (85.8 t/h, about 88 m³/h at return temperature).
Why check the margin to boiling?
High-temperature hot water must stay well below saturation at the boiler outlet, or it flashes in the tubes and pumps.
Can I use 4.187 kJ/kgK?
Close at low temperatures; IF97 enthalpies are exact at any temperature and pressure.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.