Boiler Blowdown Rate (TDS Balance)

Continuous blowdown needed to hold boiler water dissolved solids at a limit, with feedwater flow, cycles of concentration and the heat lost in the blowdown.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)BoilerBoiler attendant and boiler operator examinations

Inputs

Examples: Shell boiler 10 t/h, feed 150 ppm, limit 3 000 ppmWater-tube 50 t/h, feed 50 ppm, limit 1 500 ppmHP drum 120 t/h, feed 5 ppm, limit 150 ppm

TDS (or the controlling species, e.g. silica) by mass in the feedwater entering the drum.
The limit for the boiler pressure from the boiler maker or the water-chemistry guideline.
Absolute. Choose a gauge unit to enter gauge readings.

Results

Blowdown flow526.32kg/h
Blowdown as a share of steam5.2632%
Blowdown as a share of feedwater5.0000%
Feedwater flow10,526kg/h
Cycles of concentration20.000
Heat leaving with the blowdown (above feedwater)48.422kW
Boiler water enthalpy (saturated liquid)772.10kJ/kg
Feedwater enthalpy440.90kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Shell boiler 10 t/h, feed 150 ppm, limit 3 000 ppm. The inputs, in the units selected above:

InputValue
Steam generated10,000 kg/h
Dissolved solids in feedwater150.00 ppm
Maximum dissolved solids in boiler water3,000.0 ppm
Drum pressure (absolute)10.500 bar
Feedwater temperature105.00 °C

Applying the formula below gives:

ResultValue
Blowdown flow526.32 kg/h
Blowdown as a share of steam5.2632 %
Blowdown as a share of feedwater5.0000 %
Feedwater flow10,526 kg/h
Cycles of concentration20.000
Heat leaving with the blowdown (above feedwater)48.422 kW
Boiler water enthalpy (saturated liquid)772.10 kJ/kg
Feedwater enthalpy440.90 kJ/kg

Open this example in the calculator and change any input.

Formula

Dissolved solids enter only with the feedwater and leave only with the blowdown (steam carries none):

\(F\,c_{fw} = B\,c_{bd} \qquad F = S + B \quad\Rightarrow\quad B = \frac{S\,c_{fw}}{c_{bd} - c_{fw}}\)

\(N = \frac{c_{bd}}{c_{fw}} \qquad B/F = \frac{c_{fw}}{c_{bd}} \qquad \dot Q_{bd} = B\,(h_f - h_{fw})\)

Variables

Symbol Meaning SI unit
\(S\) steam generated kg/s
\(c_{fw}\) dissolved solids in feedwater (mass fraction) –
\(c_{bd}\) maximum dissolved solids in boiler water –
\(p\) drum absolute pressure Pa
\(T_{fw}\) feedwater temperature K
\(B\) blowdown flow kg/s
\(B/S\) blowdown as a share of steam –
\(B/F\) blowdown as a share of feedwater –
\(F\) feedwater flow kg/s
\(N\) cycles of concentration –
\(\dot Q_{bd}\) heat leaving with the blowdown, above feedwater W
\(h_{f}\) saturated liquid enthalpy at drum pressure J/kg
\(h_{fw}\) feedwater enthalpy J/kg

Method and standards

Steady-state mass balance on dissolved solids, the standard basis for continuous blowdown control. Enthalpies from FireCAD's IAPWS-IF97 implementation. Boiler-water limits are the user's input, taken from the boiler maker or a recognised water-chemistry guideline for the drum pressure.

Where it is used

  • Setting continuous blowdown of drum boilers from feedwater and boiler water TDS or silica.
  • Water treatment design: what make-up quality allows what blowdown.
  • Make-up water and chemical consumption estimates.

Common mistakes

  • Using conductivity limits from one boiler pressure for another; the limits fall as pressure rises.
  • Expressing blowdown as a share of steam in one place and of feedwater in another.
  • Forgetting that returned condensate lowers the feedwater TDS.

Assumptions and limits

  • Steady state; no solids carried over with the steam and none removed by intermittent (bottom) blowdown. At high drum pressure silica volatilises into the steam, so for silica the balance overstates the blowdown needed; use the boiler maker's silica curve.
  • A warning appears when the blowdown exceeds 10 % of the steam.
  • Concentrations by mass (ppm = mg/kg); for dilute water mg/L is the same number.
  • Feedwater enthalpy at drum pressure.

References

  • IAPWS R7-97(2012) IF97
  • boiler-water limits from the boiler maker or a water-chemistry guideline (user input)

Questions and answers

How is blowdown calculated?

By a dissolved-solids balance. Solids enter with the feedwater and leave only with the blowdown, so B = S·c_fw/(c_bd − c_fw). For 10 t/h with 150 ppm feed and a 3 000 ppm limit, B = 526 kg/h, 5.3 % of the steam.

Where do the boiler-water limits come from?

From the boiler maker or a water-chemistry guideline for the drum pressure and the controlling species (TDS, silica, alkalinity, chloride). Use the species that gives the highest blowdown.

Why does the heat loss matter?

Blowdown leaves as saturated water at drum pressure. For a 50 t/h boiler at 45 bar(a) blowing down 3.4 % of steam, about 254 kW leaves above the feedwater enthalpy; a flash vessel and cooler can recover most of it.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.