Worked example
Example: 8 kg/cm² g, 50 mm, 5 kg valve. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Blow-off pressure | 7.8453 bar g |
| Valve diameter (area the steam acts on) | 50.000 mm |
| Mass of the valve and weight carrier | 5.0000 kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Valve area | 19.635 cm² |
| Steam force on the valve | 1,540.4 N |
| Total mass to be lifted (F / g) | 157.08 kg |
| Dead weight to add | 152.08 kg |
Open this example in the calculator and change any input.
Formula
\(F = (p - p_{atm})\, \frac{\pi d^2}{4}\)
\(m_t = \frac{F}{g}, \quad m_d = m_t - m_v\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Blow-off pressure | Pa |
| \(d\) | Valve diameter (area the steam acts on) | m |
| \(m_v\) | Mass of the valve and weight carrier | kg |
| \(A\) | Valve area | m² |
| \(F\) | Steam force on the valve | N |
| \(m_t\) | Total mass to be lifted (F / g) | kg |
| \(m_d\) | Dead weight to add | kg |
Method and standards
Force balance on the valve at the lift point.
Worked example
A dead weight safety valve of 50 mm diameter must blow at 8 kg/cm² g; the valve and carrier weigh 5 kg.
- Area = π × 0.05²/4 = 19.63 cm²
- Force = 8 kg/cm² × 19.63 cm² = 157.1 kgf (1540 N)
- Dead weight = 157.1 − 5 = 152.1 kg
Where it is used
- Boiler attendant examinations.
- Low-pressure steam and hot-water vessels with weighted valves.
Common mistakes
- Using absolute pressure.
- Forgetting the valve's own weight.
- Using kgf and N in the same sum.
Assumptions and limits
- Static balance; friction neglected.
- Principle calculation, not a code sizing: accumulation, overpressure and the difference between seat and bore area are not considered.
- Gauge pressure is taken relative to the standard atmosphere; enter the gauge set pressure directly.
References
- Force balance (statics, textbook)
Questions and answers
What dead weight does a 50 mm valve need at 8 kg/cm² g?
The steam force is 1540 N, which equals 157.1 kg; with a 5 kg valve and carrier, 152.1 kg of dead weight.
Why are dead weight valves only for small, low-pressure boilers?
The weight grows with pressure times area: a 100 mm valve at 10 kg/cm² g needs about 785 kg.
Is gauge or absolute pressure used?
Gauge: the atmosphere presses on both sides.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.