Worked example
Example: 10 kg/cm² g, 80 mm valve, 100 mm / 800 mm, 10 kg lever. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Blow-off pressure | 9.8066 bar g |
| Valve diameter (area the steam acts on) | 80.000 mm |
| Fulcrum to valve centre | 100.00 mm |
| Fulcrum to the weight | 0.80000 m |
| Mass of the lever | 10.000 kg |
| Fulcrum to the lever's centre of gravity | 0.45000 m |
| Mass of the valve and spindle | 2.0000 kg |
| Weight available (to find its position) | 50.000 kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam force on the valve | 4,929.4 N |
| Weight needed at distance L | 56.957 kg |
| Distance for the weight available | 0.91131 m |
Open this example in the calculator and change any input.
Formula
\(F = (p - p_{atm})\, \frac{\pi d^2}{4}\)
\(F\, a = g\,(W L + m_l\, l_g + m_v\, a)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Blow-off pressure | Pa |
| \(d\) | Valve diameter where the disc seals on the seat (area the steam acts on) | m |
| \(a\) | Fulcrum to valve centre | m |
| \(L\) | Fulcrum to the weight | m |
| \(m_l\) | Mass of the lever | kg |
| \(l_g\) | Fulcrum to the lever's centre of gravity | m |
| \(m_v\) | Mass of the valve and spindle | kg |
| \(m_w\) | Weight available (to find its position) | kg |
| \(F\) | Steam force on the valve | N |
| \(W\) | Weight needed at distance L | kg |
| \(L_W\) | Distance for the weight available | m |
Method and standards
Moments about the fulcrum at the instant the valve lifts: the steam force at distance a balances the weight, the lever's own weight and the valve's weight.
Worked example
A lever safety valve of 80 mm diameter is 100 mm from the fulcrum. The lever weighs 10 kg with its centre 450 mm from the fulcrum, and the valve weighs 2 kg. What weight at 800 mm makes it blow at 10 kg/cm² g?
- Steam force = 10 × 98 066.5 Pa × π × 0.08²/4 = 4929 N
- Moment of steam = 4929 × 0.1 = 492.9 N·m, which is 50.26 kg·m
- Less lever 10 × 0.45 = 4.5 kg·m and valve 2 × 0.1 = 0.2 kg·m leaves 45.56 kg·m
- Weight = 45.56 / 0.8 = 57.0 kg
Where it is used
- Boiler attendant examinations (lever valves on old Lancashire and Cornish boilers).
- Checking an old lever-type valve's setting.
- Teaching moments in statics.
Common mistakes
- Using absolute pressure.
- Leaving out the lever's own weight.
- Measuring distances from the valve instead of the fulcrum.
Assumptions and limits
- Static balance; spindle friction neglected.
- The steam acts on the area at the seat sealing diameter; the force goes with its square, so use that diameter, not the inlet pipe bore.
- Atmospheric pressure is taken as the standard 101.325 kPa. Enter the blow-off pressure as gauge; an absolute pressure measured at altitude would overstate the gauge pressure by the drop in atmospheric pressure.
- Modern boilers use spring-loaded valves to code; this is a principle calculation.
References
- Moments about a fulcrum (statics, textbook)
Questions and answers
What weight does an 80 mm valve need at 800 mm to blow at 10 kg/cm² g?
The steam pushes with 4929 N, 100 mm from the fulcrum. Less the 10 kg lever (centre 450 mm) and 2 kg valve, a weight of 57.0 kg at 800 mm holds it.
Where would a 50 kg weight go?
At 911 mm from the fulcrum, beyond the 800 mm lever: a longer lever or a heavier weight is needed.
Why gauge pressure?
Atmospheric pressure acts on the outside of the valve too, so only the gauge pressure lifts it.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.