Worked example
Example: Indian coal, air 30 to 180 °C, 74 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Gross calorific value of the fuel, as fired | 18,600 kJ/kg |
| Air temperature now | 30.000 °C |
| Air temperature after preheating | 180.00 °C |
| Boiler efficiency now (on GCV) | 74.000 % |
| Fuel firing rate | 12,000 kg/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fuel saved, share | 8.0308 % |
| Fuel saved | 963.70 kg/h |
| Efficiency after | 80.462 % |
| Efficiency gain (points) | 6.4618 % |
| Heat returned in the air per kg of fuel | 1,201.9 kJ/kg |
| Air preheater duty | 4,006.3 kW |
Open this example in the calculator and change any input.
Formula
\(B_a = m_a\left[h_{air}(T_{a,2}) - h_{air}(T_{a,1})\right] + \omega\,m_a\left[h_v(T_{a,2}) - h_v(T_{a,1})\right]\)
\(\Delta\eta = \frac{B_a}{GCV} \qquad \eta_2 = \eta_1 + \Delta\eta \qquad s = 1 - \frac{\eta_1}{\eta_2} \qquad \dot Q_a = \dot m_f\,B_a\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) | ultimate analysis as fired, mass fractions | – |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(GCV\) | gross calorific value | J/kg |
| \(T_{a,1}\) | air temperature now | K |
| \(T_{a,2}\) | air temperature after preheating | K |
| \(\eta_1\) | boiler efficiency now | – |
| \(\dot m_f\) | fuel firing rate | kg/s |
| \(s\) | fuel saved, share | – |
| \(\Delta\dot m_f\) | fuel saved, \(s\,\dot m_f\) | kg/s |
| \(\eta_2\) | efficiency after | – |
| \(\Delta\eta\) | efficiency gain | – |
| \(B_a\) | heat returned in the air per kg of fuel | J/kg |
| \(\dot Q_a\) | air preheater duty | W |
| \(m_a\) | actual dry air per kg of fuel | kg/kg |
| \(h_{air}\), \(h_v\) | enthalpies of dry air and water vapour (Shomate) | J/kg |
Method and standards
Actual dry air and its moisture per kg of fuel from FireCAD's combustion balance; the heat returned by the preheated air from NIST Shomate enthalpies of dry air and water vapour. The gain in efficiency equals that heat over the GCV, which assumes the flue gas leaves at the same temperature (the air heater takes the heat from gas that would otherwise be lost).
Where it is used
- Adding an air preheater to a boiler, furnace or thermic fluid heater.
- Recuperators and regenerators on industrial furnaces.
- Valuing air heater repairs when the hot air temperature has fallen.
Common mistakes
- Counting air preheated by steam as a fuel saving.
- Forgetting that the stack temperature must stay the same for the saving to hold; a smaller air heater that also lets the gas leave hotter saves less.
- Using the hot air temperature at the heater outlet when tempering air is mixed in before the burner.
Assumptions and limits
- The heat comes from flue gas that would otherwise leave the stack; exit gas temperature unchanged.
- Same excess air before and after.
- The calculator does not check that the flue gas can supply the heat; the gas entering the air heater must be well above \(T_{a,2}\).
- The air preheater duty \(\dot Q_a\) uses the present firing rate; after the saving the fuel rate, and so the duty, is lower by the share \(s\).
- A warning appears when the GCV differs from the Channiwala–Parikh estimate of the analysis by more than 15 %.
References
- ASME PTC 4-2013 §5.15 (credit for entering air)
- NIST Chemistry WebBook Shomate equations
Questions and answers
How much fuel does preheating combustion air save?
For coal at 25 % excess air, heating the air from 30 to 180 °C returns 1.20 MJ per kg of fuel, raising efficiency from 74.0 to 80.5 % and saving 8.0 % of the fuel. The heat must come from the flue gas, not from steam.
Does it matter where the heat comes from?
Yes. Air preheated by flue gas leaving the boiler is a real saving. Air preheated by steam (a steam coil air heater) only moves heat around; it protects the air heater from corrosion but saves little fuel.
What limits the air temperature?
The flue gas available, the burner or grate (grates and some burners limit hot air), and NOx, which rises with flame temperature.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.