Worked example
Example: 0.5 t/h at 18 bar(a), flash 1.5 bar(a), drain 40 °C, make-up 5 t/h at 25 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Blowdown flow | 500.00 kg/h |
| Boiler drum pressure (absolute) | 18.000 bar |
| Flash vessel pressure (absolute) | 1.5000 bar |
| Drain temperature leaving the cooler | 40.000 °C |
| Make-up water flow through the cooler | 5,000.0 kg/h |
| Make-up water inlet temperature | 25.000 °C |
| Make-up water pressure (absolute) | 3.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat recovered | 101.21 kW |
| Share of blowdown heat recovered | 93.480 % |
| Make-up water outlet temperature | 30.819 °C |
| Flash steam fraction | 18.757 % |
| Flash steam flow | 93.784 kg/h |
| Residual blowdown to the cooler | 406.22 kg/h |
| Heat in the flash steam (above make-up temperature) | 67.420 kW |
| Heat transferred in the drain cooler | 33.785 kW |
| Heat in the blowdown (above make-up temperature) | 108.26 kW |
| Flash vessel temperature | 111.35 °C |
| Boiler water enthalpy | 884.61 kJ/kg |
| Liquid enthalpy at flash pressure | 467.08 kJ/kg |
| Flash steam enthalpy | 2,693.1 kJ/kg |
| Drain enthalpy | 167.67 kJ/kg |
Open this example in the calculator and change any input.
Formula
Flash vessel (isenthalpic flash of saturated boiler water) and drain cooler:
\(x = \frac{h_{f,b} - h_{f,f}}{h_{g,f} - h_{f,f}} \qquad \dot m_{fs} = x\,B \qquad \dot m_l = (1-x)\,B\)
\(\dot Q_{fs} = \dot m_{fs}\,(h_{g,f} - h_{mu}) \qquad \dot Q_{hx} = \dot m_l\,(h_{f,f} - h_d) \qquad \dot Q_{rec} = \dot Q_{fs} + \dot Q_{hx}\)
\(\dot Q_{bd} = B\,(h_{f,b} - h_{mu}) \qquad \eta_{rec} = \frac{\dot Q_{rec}}{\dot Q_{bd}} \qquad h_{mu,2} = h_{mu} + \frac{\dot Q_{hx}}{\dot m_{mu}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(B\) | blowdown flow | kg/s |
| \(p_b\) | boiler drum absolute pressure | Pa |
| \(p_f\) | flash vessel absolute pressure | Pa |
| \(T_d\) | drain temperature leaving the cooler | K |
| \(\dot m_{mu}\) | make-up water flow through the cooler | kg/s |
| \(T_{mu}\) | make-up water inlet temperature | K |
| \(p_{mu}\) | make-up water absolute pressure | Pa |
| \(x\) | flash steam fraction | – |
| \(\dot m_{fs}\) | flash steam flow | kg/s |
| \(\dot m_l\) | residual blowdown to the cooler | kg/s |
| \(\dot Q_{fs}\) | heat in the flash steam above make-up temperature | W |
| \(\dot Q_{hx}\) | heat transferred in the drain cooler | W |
| \(\dot Q_{rec}\) | heat recovered | W |
| \(\dot Q_{bd}\) | heat in the blowdown above make-up temperature | W |
| \(\eta_{rec}\) | share of blowdown heat recovered | – |
| \(T_{mu,2}\) | make-up water outlet temperature (from \(h_{mu,2}\)) | K |
| \(T_f\) | flash vessel saturation temperature | K |
| \(h_{f,b}\) | saturated liquid enthalpy at drum pressure | J/kg |
| \(h_{f,f}\) | saturated liquid enthalpy at flash pressure | J/kg |
| \(h_{g,f}\) | saturated vapour enthalpy at flash pressure | J/kg |
| \(h_d\) | drain enthalpy, at \(T_d\) and flash vessel pressure | J/kg |
| \(h_{mu}\) | make-up water inlet enthalpy | J/kg |
Method and standards
Energy balances on the flash vessel and the drain cooler with enthalpies from FireCAD's IAPWS-IF97 implementation. The make-up outlet temperature is found from its pressure and enthalpy (IF97 backward equation, refined on the forward equation).
Where it is used
- Continuous blowdown recovery with a flash vessel and a make-up water heat exchanger.
- Energy audits of boiler houses.
- Justifying automatic TDS control together with heat recovery.
Common mistakes
- Counting heat in flash steam that has nowhere to go.
- Ignoring scaling of the blowdown heat exchanger.
- Using the blowdown rate as a share of feedwater instead of steam.
Assumptions and limits
- Saturated blowdown at drum pressure; equilibrium flash; no carry-over of liquid with the flash steam.
- No heat loss from the vessel or cooler; the cooler is counter-flow when the make-up leaves hotter than the drain.
- The make-up water must leave the cooler colder than the blowdown enters it (the flash vessel temperature); a temperature cross is rejected.
- The flash steam is used where it condenses at the flash pressure (usually the deaerator); its heat is counted down to the make-up water temperature, which assumes the deaerator or another user can take all of it. If the deaerator already has enough heating steam, part of the flash steam is vented and the recovery is lower.
References
- IAPWS R7-97(2012) IF97
Questions and answers
How much heat can be recovered from blowdown?
With a flash vessel feeding the deaerator and a drain cooler, typically over 90 %. For 2 t/h at 45 bar(a), flashing at 2 bar(a) and cooling the drain to 35 °C against make-up at 30 °C, 545 kW of the 553 kW above make-up temperature is recovered.
Where does the flash steam go?
Usually into the deaerator at the flash vessel pressure, where it condenses and heats the feedwater. Its heat is counted above the make-up water temperature.
Why is the make-up temperature rise small?
The residual blowdown is a small flow cooled across a wide range, while the make-up flow is many times larger, so its temperature rises only a few kelvin.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.