Worked example
Example: Blowdown 40 bar to deaerator 2 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Upstream pressure (absolute) | 40.000 bar |
| Flash pressure (absolute) | 2.0000 bar |
| Condensate or blowdown flow | 2,500.0 kg/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flash steam fraction | 26.470 % |
| Flash steam flow | 661.74 kg/h |
| Remaining condensate flow | 1,838.3 kg/h |
| Upstream saturation temperature | 250.36 °C |
| Flash temperature | 120.21 °C |
| Upstream liquid enthalpy | 1,087.4 kJ/kg |
| Liquid enthalpy at flash pressure | 504.68 kJ/kg |
| Latent heat at flash pressure | 2,201.6 kJ/kg |
| Heat carried by the flash steam | 404.68 kW |
| Flash steam volume flow | 586.13 m³/h |
Open this example in the calculator and change any input.
Formula
An energy balance across the pressure drop (an isenthalpic throttling to the flash pressure):
\(x = \frac{h_{f1} - h_{f2}}{h_{fg2}} \qquad \dot m_{fs} = x\,\dot m \qquad \dot m_c = (1 - x)\,\dot m \qquad \dot Q_{fs} = \dot m_{fs}\,h_{fg2} \qquad \dot V_{fs} = \dot m_{fs}\,v_{g2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_1\) | upstream absolute pressure of the saturated liquid | Pa |
| \(p_2\) | absolute pressure after the drop (flash vessel) | Pa |
| \(\dot m\) | liquid mass flow before the drop | kg/s |
| \(x\) | mass fraction flashed to steam | – |
| \(\dot m_{fs}\) | flash steam mass flow | kg/s |
| \(\dot m_{c}\) | remaining condensate mass flow | kg/s |
| \(T_1\), \(T_2\) | saturation temperatures at \(p_1\) and \(p_2\) | K |
| \(h_{f1}\) | saturated liquid enthalpy at \(p_1\) | J/kg |
| \(h_{f2}\) | saturated liquid enthalpy at \(p_2\) | J/kg |
| \(h_{fg2}\) | latent heat of vaporisation at \(p_2\) | J/kg |
| \(\dot Q_{fs}\) | latent heat carried by the flash steam | W |
| \(\dot V_{fs}\) | volume flow of the flash steam at \(p_2\) | m³/s |
Method and standards
Enthalpies from FireCAD's IAPWS-IF97 implementation on the saturation line (region 1 liquid and region 2 vapour, region 3 above about 165 bar, region 4 pressure–temperature relation). The throttling is treated as adiabatic with no kinetic energy change, the usual assumption for flash vessels and condensate receivers.
Where it is used
- Sizing flash vessels for blowdown and condensate.
- Valuing flash steam recovery to a low-pressure header or deaerator.
- Sizing condensate return lines, which carry the flash steam as well as water.
Common mistakes
- Using gauge pressures in the flash fraction instead of absolute.
- Assuming the condensate is saturated when it is subcooled after a trap or a cooler: it flashes less.
- Sizing condensate lines for water only; the flash steam takes most of the volume.
Assumptions and limits
- Saturated liquid upstream; sub-cooled liquid flashes less.
- Equilibrium at the flash pressure; real vessels carry over a little liquid.
- Both pressures absolute and below the critical pressure (220.64 bar).
References
- IAPWS R7-97(2012) IF97
Questions and answers
Why does condensate flash at all?
Saturated water at 40 bar holds 1 087 kJ/kg. At 2 bar liquid water can hold only 505 kJ/kg, so the surplus 582 kJ/kg evaporates about 26 % of the mass into steam at 2 bar.
What if the condensate is sub-cooled before the valve?
Use the actual liquid enthalpy instead of h_f1. The calculator assumes saturated liquid upstream, which is the case for steam traps and continuous blowdown; sub-cooling reduces the flash fraction.
What is the flash steam worth?
The heat shown as "heat carried by the flash steam" is the latent heat you recover if the flash steam is used, for example in a deaerator. For 2 500 kg/h of 40 bar blowdown to 2 bar it is about 400 kW.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.