Worked example
Example: DN100 (114.3 mm) held at 60 °C, -5 °C ambient, 50 mm wool, 200 m, 4.5 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Traced pipe outer diameter | 114.30 mm |
| Insulation thickness | 50.000 mm |
| Insulation thermal conductivity | 0.045000 W/(m·K) |
| Temperature to maintain | 60.000 °C |
| Lowest design ambient temperature | -5.0000 °C |
| Emissivity of the cladding | 0.10000 - |
| Traced length | 200.00 m |
| Tracer steam pressure (absolute, saturated) | 4.5000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat loss per metre | 24.788 W/m |
| Heat loss of the traced length | 4.9576 kW |
| Tracer steam needed | 8.4178 kg/h |
| Tracer steam temperature | 147.91 °C |
| Cladding surface temperature | 4.8958 °C |
Open this example in the calculator and change any input.
Formula
\(q' = \frac{T_i - T_{sf}}{\ln(D/D_o)/(2\pi\lambda)} = h_{se}\,\pi D\,(T_{sf} - T_a) \qquad \dot Q = q' L \qquad \dot m_s = \frac{\dot Q}{h_{fg}(p_s)}\)
\(h_{se} = h_{cv} + h_r, \quad h_{cv} = 1.25\left(\frac{\Delta T}{D}\right)^{1/4}\ (D^3\Delta T \le 10\ \mathrm{m^3K}),\quad h_{cv} = 1.21\,\Delta T^{1/3}\ (D^3\Delta T > 10), \quad h_r = \varepsilon\sigma\frac{T_{sf}^4 - T_a^4}{T_{sf} - T_a}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | pipe outer diameter | m |
| \(t\) | insulation thickness | m |
| \(\lambda\) | insulation conductivity | W/(m·K) |
| \(T_i\) | temperature to maintain | K |
| \(T_a\) | design ambient | K |
| \(\varepsilon\) | cladding emissivity | – |
| \(L\) | traced length | m |
| \(p_s\) | tracer steam pressure | Pa |
| \(q'\) | loss per metre | W/m |
| \(\dot Q\) | total loss | W |
| \(\dot m_s\) | tracer steam | kg/s |
| \(T_s\) | tracer steam temperature | K |
| \(T_{sf}\) | cladding surface temperature | K |
| \(D\) | outer diameter of insulation | m |
| \(h_{se}\) | ISO 12241 surface coefficient | W/(m²·K) |
| \(h_{fg}\) | latent heat | J/kg |
| \(h_{cv}\), \(h_r\) | convection and radiation parts of \(h_{se}\) | W/(m²·K) |
| \(\Delta T\) | surface to ambient temperature difference | K |
| \(\sigma\) | Stefan–Boltzmann constant | W/(m²·K⁴) |
Method and standards
ISO 12241 insulated pipe loss in still air at the lowest design ambient; tracer steam condenses fully, IAPWS-IF97 latent heat.
Where it is used
- Fuel oil and viscous product lines.
- Instrument impulse lines.
- Frost protection of water lines.
Common mistakes
- Using normal rather than winter ambient.
- Wet or damaged insulation.
- Ignoring wind, which raises losses.
Assumptions and limits
- Still air (wind ignored); insulation dry; tracer contact and the extra area of the tracer are ignored.
- A tracer less than 10 K hotter than the pipe is flagged; the result is still shown for the heat loss.
- The temperature to maintain must be above the ambient temperature.
References
- ISO 12241
- IAPWS-IF97
Questions and answers
How much steam traces 200 m of DN100 held at 60 °C in −5 °C weather?
With 50 mm wool and aluminium cladding: 24.8 W/m, 4.96 kW in all, 8.4 kg/h of 4.5 bar(a) steam.
How hot must the tracer be?
Well above the holding temperature; here 147.9 °C against 60 °C.
Why limit tracer run length?
Long runs back up condensate; practice is a trap every 30–50 m.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.