Worked example
Example: Ganapathy: 60,000 lb/h at 650 psia, 800 °F to 15 psia. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam flow | 27,216 kg/h |
| Upstream pressure (absolute) | 44.816 bar |
| Upstream steam condition | Superheated at the temperature below |
| Upstream temperature (superheated only) | 426.67 °C |
| Pressure after throttling (absolute) | 1.0342 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Enthalpy (constant) | 3,269.5 kJ/kg |
| Temperature after throttling | 395.64 °C |
| Specific volume after throttling | 2.9804 m³/kg |
| Volume flow after throttling | 81,114 m³/h |
Open this example in the calculator and change any input.
Formula
\(h_2(p_2, T_2) = h_1(p_1, T_1), \quad \dot V_2 = \dot m\, v_2(p_2, h_1)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Steam flow | kg/s |
| \(p_1\) | Upstream pressure (absolute) | Pa |
| \(\text{state}\) | Upstream steam condition: dry saturated, or superheated at \(T_1\) | – |
| \(T_1\) | Upstream temperature (superheated only; above the saturation temperature at \(p_1\)) | K |
| \(p_2\) | Pressure after throttling (absolute) | Pa |
| \(h\) | Enthalpy (constant) | J/kg |
| \(T_2\) | Temperature after throttling | K |
| \(v_2\) | Specific volume after throttling | m³/kg |
| \(\dot V_2\) | Volume flow after throttling | m³/s |
Method and standards
Isenthalpic throttling with IF97.
Where it is used
- Vent silencer and blow-off pipe sizing.
- Start-up vent design.
Common mistakes
- Using the inlet specific volume.
- Assuming saturated steam at the outlet.
Assumptions and limits
- Adiabatic valve; kinetic energy recovered. At high outlet velocity the static temperature is lower and the volume different; keep the vent velocity well below sonic for the results to hold.
- Temperatures follow the unit system (°F in US units, as in Ganapathy's example).
- The upstream steam is dry saturated or superheated; a temperature at or below the saturation temperature is rejected (it would be water, not steam).
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q1.16 (steam volume after throttling)
- IAPWS-IF97 (isenthalpic throttling)
Questions and answers
Why is throttling isenthalpic?
No work or heat crosses the valve, and kinetic energy is recovered downstream, so enthalpy stays constant.
Why does superheated steam stay superheated?
Expanding to low pressure at constant enthalpy moves the state further into the superheat region.
What does Ganapathy's example give?
60,000 lb/h at 650 psia, 800 °F throttled to 15 psia: 745 °F and 48 ft³/lb, 2.88 million ft³/h.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.