Worked example
Example: Water 5 kg/s from 20 to 80 °C, steam 6 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid flow to heat | 18,000 kg/h |
| Specific heat of the liquid | 4.1800 kJ/(kg·K) |
| Liquid temperature in | 20.000 °C |
| Liquid temperature out | 80.000 °C |
| Steam pressure (absolute, saturated) | 6.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam needed | 1,864.9 kg/h |
| Steam per kg of liquid | 0.10360 kg/kg |
| Liquid flow out (diluted by condensate) | 19,865 kg/h |
Open this example in the calculator and change any input.
Formula
\(\dot m_s = \frac{\dot m\,c_p\,(T_2 - T_1)}{h_g - h_l(T_2)} \qquad \dot m_2 = \dot m + \dot m_s\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | liquid flow | kg/s |
| \(c_p\) | liquid specific heat | J/(kg·K) |
| \(T_1\) | liquid in | K |
| \(T_2\) | liquid out | K |
| \(p_s\) | steam pressure | Pa |
| \(\dot m_s\) | steam needed | kg/s |
| \(\dot m_s/\dot m\) | steam per kg of liquid | kg/kg |
| \(\dot m_2\) | liquid out | kg/s |
| \(h_g\) | saturated steam enthalpy (IF97) | J/kg |
| \(h_l\) | enthalpy of the condensate at T₂, taken at the steam pressure (IF97) | J/kg |
Method and standards
Energy balance with the steam condensing completely and leaving at the outlet temperature.
Where it is used
- Hot water generation, CIP and process water heating.
- Cooking, starch and pulp heating.
- Comparing direct and indirect heating.
Common mistakes
- Forgetting dilution of the product.
- Injecting too much steam at once (hammer, uncondensed steam).
- Counting the condensate as returned make-up.
Assumptions and limits
- Complete condensation; no heat loss; saturated steam.
- The condensate enthalpy is taken at the steam pressure; for liquid water its pressure hardly matters.
- Above about 100 °C the product must be pressurised so it does not boil; the liquid pressure is not an input, and a warning appears.
- The steam-to-liquid ratio is shown even for zero flow.
References
- Energy balance
- IAPWS R7-97 IF97
Questions and answers
How much steam heats water by injection?
5 kg/s of water from 20 to 80 °C with 6 bar(a) steam needs 0.52 kg/s (1865 kg/h), about 10 % of the water flow.
Why less steam than indirect heating?
All the steam's heat stays in the liquid, including the condensate's own heat; with a coil the condensate leaves hot.
What are the drawbacks?
The product is diluted by the condensate, the steam must be clean, and the condensate is not returned to the boiler.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.