Deaerator Heating Steam Consumption

Heating steam a deaerator needs to bring feedwater to saturation at its operating pressure, from a mass and energy balance with vent loss (IAPWS-IF97).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)Deaerator and feedwater systemBoiler operation engineer (BOE) examinations

Inputs

Examples: Process deaerator 0.2 bar g, 50 t/h, water 80 °C, steam 3 bar(a) saturatedPower plant deaerator 6 bar(a), 300 t/h, water 140 °C, extraction 7 bar(a) / 250 °CSmall deaerator 1.3 bar(a), 10 t/h, water 60 °C, steam 4 bar(a) saturated

Deaerator

Absolute; choose a gauge unit to enter, for example, 0.2 bar g.
Saturated steam lost through the vent with the gases; 0 to ignore.

Inlet water

Heating steam

Results

Heating steam flow2,210.0kg/h
Inlet water flow47,790kg/h
Steam per kg of feedwater4.4200%
Deaerator (saturation) temperature105.10°C
Inlet water enthalpy335.01kJ/kg
Heating steam enthalpy2,724.9kJ/kg
Outlet feedwater enthalpy (saturated liquid)440.64kJ/kg
Vent steam enthalpy (saturated vapour)2,683.5kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Process deaerator 0.2 bar g, 50 t/h, water 80 °C, steam 3 bar(a) saturated. The inputs, in the units selected above:

InputValue
Deaerated feedwater outlet flow50,000 kg/h
Deaerator pressure (absolute)1.2132 bar
Vent steam flow0 kg/h
Inlet water temperature (condensate and make-up, mixed)80.000 °C
Heating steam pressure (absolute)3.0000 bar
Heating steam conditionDry saturated
Heating steam temperature (superheated only)250.00 °C

Applying the formula below gives:

ResultValue
Heating steam flow2,210.0 kg/h
Inlet water flow47,790 kg/h
Steam per kg of feedwater4.4200 %
Deaerator (saturation) temperature105.10 °C
Inlet water enthalpy335.01 kJ/kg
Heating steam enthalpy2,724.9 kJ/kg
Outlet feedwater enthalpy (saturated liquid)440.64 kJ/kg
Vent steam enthalpy (saturated vapour)2,683.5 kJ/kg

Open this example in the calculator and change any input.

Formula

Mass and energy balances on the deaerator, outlet saturated liquid and vent saturated vapour at \(p_d\):

\(\dot m_w + \dot m_s = \dot m_{out} + \dot m_v\)

\(\dot m_w h_w + \dot m_s h_s = \dot m_{out} h_{f,d} + \dot m_v h_{g,d}\)

\(\dot m_s = \frac{\dot m_{out}\,(h_{f,d} - h_w) + \dot m_v\,(h_{g,d} - h_w)}{h_s - h_w}\)

Variables

Symbol Meaning SI unit
\(\dot m_{out}\) deaerated feedwater outlet flow kg/s
\(p_d\) deaerator absolute pressure Pa
\(\dot m_v\) vent steam flow kg/s
\(T_w\) mixed inlet water temperature K
\(p_s\) heating steam absolute pressure Pa
\(\text{state}\) dry saturated, or superheated at \(T_s\) –
\(T_s\) heating steam temperature when superheated K
\(\dot m_s\) heating steam flow kg/s
\(\dot m_w\) inlet water flow kg/s
\(\dot m_s / \dot m_{out}\) steam per kg of feedwater –
\(T_d\) deaerator saturation temperature K
\(h_w\) inlet water enthalpy J/kg
\(h_s\) heating steam enthalpy J/kg
\(h_{f,d}\) saturated liquid enthalpy at \(p_d\) J/kg
\(h_{g,d}\) saturated vapour enthalpy at \(p_d\) J/kg

Method and standards

First-law balance on a direct-contact heater, enthalpies from FireCAD's IAPWS-IF97 implementation. Steam throttled from \(p_s\) to \(p_d\) keeps its enthalpy.

Where it is used

  • Sizing deaerator heating steam and the pegging steam line.
  • Heat balances of feedwater systems with condensate return.
  • Checking deaerator pressure control at part load.

Common mistakes

  • Forgetting the vent steam.
  • Using cold make-up temperature when the make-up is preheated by blowdown or flash recovery.
  • Ignoring hot condensate return, which can make the deaerator need almost no steam.

Assumptions and limits

  • No heat loss from the deaerator shell.
  • Inlet streams (condensate, make-up, flash steam returns) are entered as one mixed water stream; add other steam inputs to the heating steam or work them out separately.
  • Outlet water leaves saturated at deaerator pressure.
  • The inlet water enthalpy is taken at the deaerator pressure, not its own line pressure; for liquid water the difference is negligible.
  • The heating steam pressure must be at least the deaerator pressure.

References

  • IAPWS R7-97(2012) IF97

Questions and answers

How much steam does a deaerator use?

For 50 t/h of feedwater at 0.2 bar g (105.1 °C) from water at 80 °C, with dry saturated steam at 3 bar(a), about 0.614 kg/s (2.2 t/h), or 4.4 % of the outlet flow.

Why include the vent?

The vent releases non-condensable gases with a little steam. That steam leaves as saturated vapour at deaerator pressure and must be supplied too; the deaerator maker gives the vent rate; it is small, a fraction of a per cent of the outlet flow.

What if the inlet water is already hot?

If the mixed inlet is at or above the deaerator saturation temperature, no heating steam is needed and the water flashes instead; the calculator stops with a message.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.