Worked example
Example: Start-up vent 40 mm from 66 bar(a) / 485 °C to atmosphere. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Upstream pressure (absolute) | 66.000 bar |
| Steam condition | Superheated at the temperature below |
| Steam temperature (superheated only) | 485.00 °C |
| Diameter of the opening | 40.000 mm |
| Discharge coefficient | 0.85000 - |
| Downstream pressure (absolute) | 1.0132 bar |
| Isentropic exponent of steam | 1.3000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam flow | 29,472 kg/h |
| Choked (1 = yes) | 1.0000 |
| Critical (choking) downstream pressure | 36.018 bar |
| Critical pressure ratio | 0.54573 |
| Specific volume upstream | 0.050026 m³/kg |
| Area of the opening | 1,256.6 mm² |
Open this example in the calculator and change any input.
Formula
\(r_c = \left(\frac{2}{k+1}\right)^{\frac{k}{k-1}} \qquad p_c = r_c\,p_0 \qquad A = \frac{\pi d^2}{4}\)
Choked (\(p_b/p_0 \le r_c\)):
\(\dot m = C_d\,A\,\sqrt{\frac{k\,p_0}{v_0}}\left(\frac{2}{k+1}\right)^{\frac{k+1}{2(k-1)}}\)
Not choked, with \(r = p_b/p_0\):
\(\dot m = C_d\,A\,\sqrt{\frac{2\,p_0}{v_0}\cdot\frac{k}{k-1}\left(r^{2/k} - r^{(k+1)/k}\right)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_0\) | upstream pressure, absolute | Pa |
| \(\text{state}\) | dry saturated or superheated steam | – |
| \(T_s\) | steam temperature (superheated) | K |
| \(d\) | diameter of the opening | m |
| \(C_d\) | discharge coefficient | – |
| \(p_b\) | downstream pressure, absolute | Pa |
| \(k\) | isentropic exponent of steam | – |
| \(\dot m\) | steam flow | kg/s |
| \(\text{choked}\) | 1 when the flow is choked | – |
| \(p_c\) | critical downstream pressure | Pa |
| \(r_c\) | critical pressure ratio | – |
| \(v_0\) | specific volume upstream | m³/kg |
| \(A\) | area of the opening | m² |
Method and standards
Isentropic flow of a gas with constant exponent k through a nozzle, with the upstream specific volume from FireCAD's IAPWS-IF97. k = 1.3 for superheated and 1.135 for dry saturated steam are the classical values (Zeuner).
Where it is used
- Estimating steam lost through vents, leaks and open drains.
- Valuing steam leak repairs.
- Sizing start-up vents.
Common mistakes
- Using gauge pressure as absolute.
- Ignoring choked flow at high pressure ratio.
- Assuming a round hole when the leak is a crack.
Assumptions and limits
- Steam treated as a gas with a constant isentropic exponent. This is an approximation; it is not compared here with a homogeneous-equilibrium calculation. Dry saturated steam turns wet as it expands, and Zeuner's 1.135 is an empirical exponent for that wet expansion.
- k should match the steam state; a mismatch is flagged.
- Upstream velocity neglected (opening small against the pipe).
- Not a safety-valve calculation: relieving capacities are certified to the pressure-vessel code.
References
- Isentropic nozzle flow (Shapiro; Perry’s Chemical Engineers’ Handbook)
- IAPWS R7-97(2012) IF97
Questions and answers
How much steam does a leak lose?
A 3 mm hole in a 10.5 bar(a) saturated steam line passes about 31 kg/h (0.0086 kg/s) with a discharge coefficient of 0.8: about 250 t of steam a year.
What is choked flow?
When the downstream pressure is below about 58 % of the upstream pressure (55 % for superheated steam), the steam reaches sonic velocity in the opening and the flow no longer depends on the downstream pressure.
Which discharge coefficient?
About 0.6–0.65 for a sharp-edged hole or orifice plate, 0.8–0.9 for a short pipe or open valve, close to 1 for a well-rounded nozzle.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.