FireCADCalc

Steam Leak Loss and Cost per Year

Steam lost through a leak or a failed-open trap orifice of a given size at line pressure, in kg/h and tonnes a year, and its cost (IAPWS-IF97, nozzle flow).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)Flash vessel and condensate

Inputs

Examples: 3 mm hole at 10 bar g saturatedFailed trap 6 mm orifice at 7 bar g1.5 mm at 40 bar(a) 400 °C

About 0.6–0.65 for a sharp-edged hole; 0.8–0.9 for a trap orifice or short nozzle.
1.135 for dry saturated steam; 1.3 for superheated steam.

Results

Dry steam only: a leak or trap passing condensate flashes, and the flow can differ greatly.

Steam lost26.207kg/h
Steam lost per year209.66t
Cost per year (your currency)524,140
Choked flow (1 = yes)1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 mm hole at 10 bar g saturated. The inputs, in the units selected above:

InputValue
Hole or orifice diameter3.0000 mm
Steam pressure (shown as gauge)10.000 bar g
Steam conditionDry saturated
Steam temperature (superheated only)250.00 °C
Discharge coefficient65.000 %
Isentropic exponent of steam1.1350 -
Pressure outside (absolute)101.33 kPa
Hours a year the line is live8,000.0 h
Cost of steam per tonne (your currency)2,500.0 -

Applying the formula below gives:

ResultValue
Steam lost26.207 kg/h
Steam lost per year209.66 t
Cost per year (your currency)524,140
Choked flow (1 = yes)1.0000

Open this example in the calculator and change any input.

Formula

\(\dot m = C_d A \sqrt{\frac{k\,p_0}{v_0}}\left(\frac{2}{k+1}\right)^{\frac{k+1}{2(k-1)}} \text{ (choked)} \qquad m_y = \dot m\,t_y \qquad C_y = \frac{m_y}{1000\ \mathrm{kg/t}}\,c_s\)

Variables

Symbol Meaning SI unit
\(d\) hole diameter m
\(p_0\) steam pressure Pa
\(\text{state}\) saturated or superheated –
\(T_s\) steam temperature K
\(C_d\) discharge coefficient –
\(k\) isentropic exponent –
\(p_b\) outside pressure Pa
\(t_y\) hours per year s
\(c_s\) cost of steam per tonne currency
\(\dot m\) steam lost kg/s
\(m_y\) steam lost per year kg
\(C_y\) cost per year currency
\(\text{choked}\) choked flow flag –
\(A\) hole area m²
\(v_0\) IF97 specific volume m³/kg

Method and standards

Isentropic nozzle flow of a perfect gas with the steam's IF97 specific volume (Zeuner exponent 1.135 for saturated steam).

Where it is used

  • Steam trap surveys.
  • Leak repair priorities.
  • Energy audits.

Common mistakes

  • Using Cd of 1.
  • Counting hours when the line is shut.
  • Valuing steam at fuel cost only.

Assumptions and limits

  • Round hole; no upstream pressure drop; wet steam not covered. Condensate-laden leaks (real trap blow-through) flash in the hole, which changes the flow considerably.
  • The steam pressure is shown as gauge in every unit system (bar g, kg/cm² g, psig).
  • k should match the steam state (1.135 dry saturated, about 1.3 superheated); a mismatch is flagged.

References

  • IAPWS-IF97
  • Isentropic nozzle flow

Questions and answers

What does a 3 mm leak at 10 bar g lose?

26.2 kg/h of saturated steam, 210 t a year at 8000 h; at 2500 per tonne, 524 000 a year.

Is a failed trap the same?

A trap failed open blows through its orifice; enter the orifice size and a discharge coefficient near 0.85.

Why is the flow choked?

Above about 0.8 bar g steam leaving to atmosphere reaches sonic speed in the hole.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.