Worked example
Example: PRDS 64 bar(a) / 480 °C to 12 bar(a) / 250 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inlet steam flow | 20,000 kg/h |
| Inlet steam pressure (absolute) | 64.000 bar |
| Inlet steam temperature | 480.00 °C |
| Outlet steam pressure (absolute) | 12.000 bar |
| Outlet steam temperature (target) | 250.00 °C |
| Spray water pressure (absolute) | 80.000 bar |
| Spray water temperature | 130.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Spray water flow | 3,644.7 kg/h |
| Outlet steam flow | 23,645 kg/h |
| Spray water per kg of inlet steam | 18.224 % |
| Saturation temperature at the outlet | 187.96 °C |
| Outlet superheat | 62.035 K |
| Inlet steam enthalpy | 3,370.1 kJ/kg |
| Outlet steam enthalpy | 2,935.7 kJ/kg |
| Spray water enthalpy | 551.64 kJ/kg |
Open this example in the calculator and change any input.
Formula
Mass and energy balance across the desuperheater (throttling, if any, is adiabatic):
\(\dot m_1 h_1 + \dot m_w h_w = \dot m_2 h_2 \qquad \dot m_2 = \dot m_1 + \dot m_w\)
\(\dot m_w = \dot m_1\,\frac{h_1 - h_2}{h_2 - h_w} \qquad \Delta T_{sh,2} = T_2 - T_{sat,2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_1\) | inlet steam flow | kg/s |
| \(p_1\) | inlet steam absolute pressure | Pa |
| \(T_1\) | inlet steam temperature | K |
| \(p_2\) | outlet steam absolute pressure | Pa |
| \(T_2\) | outlet steam temperature (target) | K |
| \(p_w\) | spray water absolute pressure | Pa |
| \(T_w\) | spray water temperature | K |
| \(\dot m_w\) | spray water flow | kg/s |
| \(\dot m_2\) | outlet steam flow | kg/s |
| \(\dot m_w / \dot m_1\) | spray water per kg of inlet steam | – |
| \(T_{sat,2}\) | saturation temperature at the outlet pressure | K |
| \(\Delta T_{sh,2}\) | outlet superheat | K |
| \(h_1\) | inlet steam enthalpy | J/kg |
| \(h_2\) | outlet steam enthalpy | J/kg |
| \(h_w\) | spray water enthalpy | J/kg |
Method and standards
Enthalpies from FireCAD's IAPWS-IF97 implementation (regions 2 and 3, or supercritical, for the steam as the state requires; region 1 for the spray water). The balance is the standard first-law statement for an adiabatic mixing device with no shaft work.
Where it is used
- Sizing PRDS spray water and attemperator flows.
- Checking spray control valves at minimum and maximum load.
- Process steam supply at a fixed superheat.
Common mistakes
- Desuperheating too close to saturation: spray water stays as droplets.
- Using spray water colder than design, which needs less water but evaporates more slowly.
- Forgetting the spray water adds to the outlet steam flow.
Assumptions and limits
- No heat loss from the desuperheater and piping.
- Warnings appear when the outlet pressure is above the inlet pressure or the spray water pressure is not above the outlet steam pressure.
- All spray water evaporates; the outlet is superheated steam.
- Inlet and outlet steam must be superheated; spray water must be liquid.
- A warning is given when the outlet superheat is below 5 K: the spray may not evaporate completely.
- At or above the critical pressure (22.064 MPa) there is no saturation temperature, so the saturation temperature and superheat are not shown.
References
- IAPWS R7-97(2012) IF97
Questions and answers
How much spray water does a PRDS need?
For 20 t/h of steam at 64 bar(a) and 480 °C reduced to 12 bar(a) and 250 °C with spray water at 130 °C, about 1.01 kg/s (3.6 t/h), or 18 % of the inlet steam. The outlet flow is the inlet steam plus the spray.
Can I desuperheat to saturation?
Not with this balance. Spray desuperheaters need some superheat at the outlet (commonly at least a few kelvin) to evaporate every droplet; the calculator requires a target above the saturation temperature.
Does the spray water pressure matter?
Only through the water enthalpy, which changes little with pressure. It must be above the steam pressure for the water to enter the nozzles.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.