Worked example
Example: 10 t of water 20 to 80 °C, coil 5 m², U 800, steam 4 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid in the tank | 10.000 t |
| Specific heat of the liquid | 4.1800 kJ/(kg·K) |
| Starting temperature | 20.000 °C |
| Final temperature | 80.000 °C |
| Overall heat transfer coefficient of coil or jacket | 800.00 W/(m²·K) |
| Coil or jacket area | 5.0000 m² |
| Steam pressure (absolute, saturated) | 4.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat-up time | 1.9284 h |
| Steam used for the batch | 1,175.6 kg |
| Average steam flow | 609.63 kg/h |
| Heat flow at the start (peak) | 494.45 kW |
| Steam saturation temperature | 143.61 °C |
Open this example in the calculator and change any input.
Formula
\(t = \frac{m c_p}{U A}\ln\frac{T_s - T_0}{T_s - T_1} \qquad m_s = \frac{m c_p (T_1 - T_0)}{h_{fg}} \qquad \dot Q_0 = U A (T_s - T_0)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m\) | liquid mass | kg |
| \(c_p\) | specific heat | J/(kg·K) |
| \(T_0\) | starting temperature | K |
| \(T_1\) | final temperature | K |
| \(U\) | overall coefficient | W/(m²·K) |
| \(A\) | coil or jacket area | m² |
| \(p_s\) | steam pressure | Pa |
| \(t\) | heat-up time | s |
| \(m_s\) | steam for the batch | kg |
| \(\bar{\dot m}_s\) | average steam flow | kg/s |
| \(\dot Q_0\) | heat flow at the start | W |
| \(T_s\) | steam saturation temperature | K |
| \(h_{fg}\) | latent heat (IF97) | J/kg |
Method and standards
Lumped (well-mixed) batch heated by condensing steam at constant temperature; U constant.
Where it is used
- Batch reactors, dissolving tanks and process vessels.
- Sizing coils and jackets for a heat-up time.
- Steam trap and steam supply sizing (peak load).
Common mistakes
- Sizing steam traps on the average instead of the start-up load.
- Ignoring tank heat loss for long heat-ups.
- Using a U for an agitated vessel when it is not stirred.
Assumptions and limits
Steam enters dry and saturated and leaves as condensate at saturation temperature, so each kilogram gives up h_fg. Wet steam, sub-cooled condensate, trap losses and flash steam are not included: wet steam needs more, sub-cooling a little less.
Well-mixed liquid; constant U and steam temperature; no heat loss.
References
- Transient heating with constant steam temperature (lumped batch)
- IAPWS R7-97 IF97
Questions and answers
How long does a tank take to heat?
10 t of water from 20 to 80 °C with a 5 m² coil at U = 800 W/(m²·K) and 4 bar(a) steam takes 1.9 hours and 1176 kg of steam; the peak heat flow at the start is 495 kW.
Why does heating slow down?
The temperature difference to the steam shrinks as the batch warms, so the rate falls exponentially.
How do I speed it up?
Raise the steam pressure (hotter steam), add area, or agitate to raise U.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.