Worked example
Example: 50 m3 oil, 70 °C, 12 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid volume | 50.000 m³ |
| Liquid density | 950.00 kg/m³ |
| Specific heat | 2.0000 kJ/(kg·K) |
| Overall coefficient to ambient | 1.2000 W/(m²·K) |
| Surface area losing heat | 90.000 m² |
| Initial temperature | 70.000 °C |
| Ambient temperature | 15.000 °C |
| Time without heating | 12.000 h |
| Lowest acceptable temperature | 50.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Temperature after the period | 67.364 °C |
| Heat lost | 69.558 kWh |
| Time constant mc_p/UA | 244.34 h |
| Time to fall to the lowest acceptable temperature | 110.44 h |
Open this example in the calculator and change any input.
Formula
\(T(t) = T_a + (T_0 - T_a)e^{-t/\tau}, \quad \tau = \frac{mc_p}{UA}, \quad t_{min} = \tau\ln\frac{T_0 - T_a}{T_{min} - T_a}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Liquid volume | m³ |
| \(\rho\) | Liquid density | kg/m³ |
| \(c_p\) | Specific heat | J/(kg·K) |
| \(U\) | Overall coefficient to ambient | W/(m²·K) |
| \(A\) | Surface area losing heat | m² |
| \(T_0\) | Initial temperature | K |
| \(T_a\) | Ambient temperature | K |
| \(t\) | Time without heating | s |
| \(T_{min}\) | Lowest acceptable temperature | K |
| \(T(t)\) | Temperature after the period | K |
| \(Q\) | Heat lost | J |
| \(\tau\) | Time constant mc_p/UA | s |
| \(t_{min}\) | Time to fall to the lowest acceptable temperature | s |
Method and standards
Lumped-capacitance cooling.
Where it is used
- Fuel oil, molasses and wax tanks.
- Hot water and process liquid storage.
Common mistakes
- Using U without the outside film.
- Ignoring the roof and bottom area.
Assumptions and limits
The time to the lowest acceptable temperature is shown only when that temperature lies between ambient and the starting temperature; the other results do not depend on it.
Well mixed; constant U and ambient.
References
- Lumped exponential cooling (Newton's law of cooling; definitions)
Questions and answers
What is the time constant?
The time for the temperature excess over ambient to fall to 37 %: the liquid's heat capacity divided by UA.
How do I get U?
From insulation thickness and outside film coefficient; an insulated tank is typically 0.3–1 W/(m²·K), bare steel 5–15.
What do the defaults give?
50 m³ of oil at 70 °C, UA 108 W/K: about 67 °C after 12 hours (time constant about 10 days).