Worked example
Example: Condenser test. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Measured duty | 5,000.0 kW |
| Heat-transfer area | 400.00 m² |
| Mean temperature difference (LMTD × F for multipass exchangers) | 25.000 K |
| Design (clean) coefficient | 650.00 W/(m²·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Measured coefficient | 500.00 W/(m²·K) |
| Cleanliness factor U/U_c | 76.923 % |
| Implied fouling resistance | 4.6154e-04 m²·K/W |
Open this example in the calculator and change any input.
Formula
\(U = \frac{\dot Q}{A\Delta T_{lm}}, \quad CF = \frac{U}{U_c}, \quad R_f = \frac{1}{U} - \frac{1}{U_c}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | Measured duty | W |
| \(A\) | Heat-transfer area | m² |
| \(\Delta T_{lm}\) | Mean temperature difference (LMTD × F for multipass exchangers) | K |
| \(U_c\) | Design (clean) coefficient | W/(m²·K) |
| \(U\) | Measured coefficient | W/(m²·K) |
| \(CF\) | Cleanliness factor U/U_c | - |
| \(R_f\) | Implied fouling resistance | m²·K/W |
Method and standards
Definitions.
Where it is used
- Condenser, heater and evaporator monitoring.
Common mistakes
- Arithmetic ΔT used for LMTD.
Assumptions and limits
- Steady state.
- For multipass or cross-flow exchangers enter F × LMTD: with the plain LMTD the measured U comes out low by the factor F.
References
- U = Q/(A ΔT_lm); CF = U/U_clean; R_f = 1/U − 1/U_clean
Questions and answers
Why trend it?
A falling cleanliness factor shows when cleaning pays.
Different flow than design?
Correct the clean U for the actual velocities before comparing.
Negative fouling resistance?
The exchanger is doing better than the design value, often because the design U was conservative.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.