Worked example
Example: 1 m wall at 70 °C in 20 °C air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fluid | Air (dry) |
| Surface temperature | 70.000 °C |
| Fluid temperature away from the surface | 20.000 °C |
| Height of the plate | 1.0000 m |
| Width of the plate | 1.0000 m |
| Pressure (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Rayleigh number at the film temperature | 3.7579e+09 |
| Nusselt number | 186.39 |
| Convection coefficient | 4.9070 W/(m²·K) |
| Heat flow from one face of the plate | 245.35 W |
Open this example in the calculator and change any input.
Formula
\(Ra_L = \frac{g\beta\,\Delta T\, L^3}{\nu\alpha}, \quad \overline{Nu}_L = \left\{0.825 + \frac{0.387 Ra_L^{1/6}}{\left[1 + (0.492/Pr)^{9/16}\right]^{8/27}}\right\}^2, \quad h = \frac{Nu\, k}{L}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{fluid}\) | Fluid | - |
| \(T_s\) | Surface temperature | K |
| \(T_\infty\) | Fluid temperature away from the surface | K |
| \(L\) | Height of the plate | m |
| \(W\) | Width of the plate | m |
| \(p\) | Pressure (absolute) | Pa |
| \(Ra\) | Rayleigh number at the film temperature | - |
| \(Nu\) | Nusselt number | - |
| \(h\) | Convection coefficient | W/(m²·K) |
| \(\dot Q\) | Heat flow from one face of the plate | W |
Method and standards
Churchill–Chu correlation for all Rayleigh numbers.
Where it is used
- Heat loss from tanks, walls and panels.
- Heat transfer examinations.
Common mistakes
- Ignoring radiation.
- Properties at the wrong temperature.
Assumptions and limits
- Isothermal vertical surface, quiescent fluid; heat flow from one face of area L × W.
- Water at or above its boiling point is rejected (boiling is not covered).
References
- S.W. Churchill and H.H.S. Chu
- Int. J. Heat Mass Transfer 18 (1975) 1323
- Incropera
- DeWitt
- Bergman and Lavine
- Fundamentals of Heat and Mass Transfer
- ch. 9
- Air from NIST Shomate
- Sutherland and Eucken (engine); water from IAPWS-IF97 and the IAPWS 2008/2011 transport releases
Questions and answers
What h does a 1 m wall at 70 °C give in 20 °C air?
About 4.9 W/(m²·K), around 245 W per m² of wall.
Why the film temperature?
Properties are taken midway between surface and fluid.
What about radiation?
Add it: at these temperatures a painted surface radiates about as much again.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.