Worked example
Example: 50 mm pipe at 100 °C in 5 m/s wind. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fluid | Air (dry) |
| Approach velocity | 5.0000 m/s |
| Outside diameter | 50.000 mm |
| Surface temperature | 100.00 °C |
| Fluid temperature | 20.000 °C |
| Pressure (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reynolds number | 13,258 |
| Average Nusselt number | 63.701 |
| Average convection coefficient | 34.763 W/(m²·K) |
| Heat flow per metre | 436.84 W/m |
Open this example in the calculator and change any input.
Formula
\(\overline{Nu}_D = 0.3 + \frac{0.62 Re_D^{1/2} Pr^{1/3}}{\left[1 + (0.4/Pr)^{2/3}\right]^{1/4}}\left[1 + \left(\frac{Re_D}{282\,000}\right)^{5/8}\right]^{4/5}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{fluid}\) | Fluid | - |
| \(V\) | Approach velocity | m/s |
| \(D\) | Outside diameter | m |
| \(T_s\) | Surface temperature | K |
| \(T_\infty\) | Fluid temperature | K |
| \(p\) | Pressure (absolute) | Pa |
| \(Re_D\) | Reynolds number | - |
| \(Nu_D\) | Average Nusselt number | - |
| \(\bar h\) | Average convection coefficient | W/(m²·K) |
| \(q'\) | Heat flow per metre | W/m |
Method and standards
Churchill–Bernstein correlation.
Where it is used
- Outdoor pipe losses.
- Thermowell and sensor heat transfer.
Common mistakes
- Using tube-bank values for a single tube.
- Free-stream properties.
Assumptions and limits
- Single cylinder, uniform approach flow.
- Single-phase: for water a surface at or above the saturation temperature (boiling) is flagged.
References
- S.W. Churchill and M. Bernstein
- J. Heat Transfer 99 (1977) 300
- Incropera
- DeWitt
- Bergman and Lavine
- Fundamentals of Heat and Mass Transfer
- ch. 7
- Air from NIST Shomate
- Sutherland and Eucken (engine); water from IAPWS-IF97 and the IAPWS 2008/2011 transport releases
Questions and answers
A 50 mm pipe at 100 °C in a 5 m/s wind?
Re about 1.3 × 10⁴, h about 35 W/(m²·K), roughly 440 W per metre.
Why does wind raise heat loss so much?
Forced convection is several times natural convection.
Valid for which range?
All Re·Pr above 0.2.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.