Worked example
Example: Oil cooler 500 kW, U 300 W/m²K, counterflow. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat duty | 500.00 kW |
| Overall heat transfer coefficient | 300.00 W/(m²·K) |
| Hot stream inlet | 150.00 °C |
| Hot stream outlet | 90.000 °C |
| Cold stream inlet | 30.000 °C |
| Cold stream outlet | 70.000 °C |
| Flow arrangement | Counterflow |
| LMTD correction factor (1 for pure counterflow) | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat transfer area required | 23.974 m² |
| Conductance required | 7.1921 kW/K |
| Log mean temperature difference | 69.521 K |
| Corrected mean temperature difference | 69.521 K |
Open this example in the calculator and change any input.
Formula
\(A = \frac{Q}{U\,F\,\Delta T_{lm}} \qquad UA = \frac{Q}{F\,\Delta T_{lm}} \qquad \Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1/\Delta T_2)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | heat duty | W |
| \(U\) | overall heat transfer coefficient | W/(m²·K) |
| \(T_{h,in}\) | hot stream inlet temperature | K |
| \(T_{h,out}\) | hot stream outlet temperature | K |
| \(T_{c,in}\) | cold stream inlet temperature | K |
| \(T_{c,out}\) | cold stream outlet temperature | K |
| \(\text{flow}\) | counterflow or parallel flow | – |
| \(F\) | LMTD correction factor | – |
| \(A\) | heat transfer area required | m² |
| \(UA\) | conductance required | W/K |
| \(\Delta T_{lm}\) | log mean temperature difference | K |
| \(F\,\Delta T_{lm}\) | corrected mean temperature difference | K |
| \(\Delta T_1\), \(\Delta T_2\) | terminal temperature differences | K |
Method and standards
The rate equation of a heat exchanger with the log mean temperature difference (Incropera, ch. 11). F for multi-pass and cross-flow arrangements comes from the charts for the exchanger type (TEMA, textbooks).
Where it is used
- First sizing of shell-and-tube and plate exchangers.
- Checking an exchanger for a new duty.
- Comparing clean and fouled performance.
Common mistakes
- Using a clean U without fouling factors.
- Taking the LMTD without the multipass correction.
- Mixing inside and outside area as the basis of U.
Assumptions and limits
- Constant U along the exchanger. For a condensing or desuperheating section, split the exchanger into zones and add the areas.
- The duty must agree with both streams' heat balances; check them with the steam or gas property calculators.
- No allowance for plugged tubes or extra surface margin; add the design margin you need.
- F applies to the counterflow LMTD; F below 1 with parallel flow, and F below 0.75, are flagged.
References
- Incropera
- Fundamentals of Heat and Mass Transfer
- ch. 11; TEMA (F factor charts)
Questions and answers
How do I find the area of a heat exchanger?
A = Q/(U·F·LMTD). A 500 kW oil cooler with U = 300 W/(m²·K) and an LMTD of 69.5 K needs 24.0 m².
Where does U come from?
From the film coefficients of both streams, the wall and the fouling factors, or from the maker's data for the exchanger type. The calculator takes it as your input; the area is on the same basis as U (usually the tube outside area).
Why is an economiser so large?
Gas-side coefficients are low. A 4.2 MW economiser with U = 45 W/(m²·K) and a corrected mean difference of 120 K needs about 778 m².
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.