FireCADCalc

Pipe Pressure Drop (Darcy–Weisbach)

Pressure drop and head loss in a pipe or round duct by Darcy–Weisbach with the Colebrook friction factor, including fittings, with velocity and Reynolds number.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliserThermic fluid heatingPump

Inputs

Examples: Water 50 m³/h in DN100 (102.3 mm), 100 m, steel 0.045 mmFeedwater 60 m³/h in DN80 (77.9 mm), 40 m, fittings K = 6Fuel oil 5 m³/h in DN50 (52.5 mm), 30 m, 180 cP (laminar)Air 2 m³/s in a 400 mm duct, 50 m, sheet steel 0.15 mm

Commercial steel 0.045 mm; drawn tubing 0.0015 mm; galvanised steel 0.15 mm; cast iron 0.26 mm; concrete 0.3–3 mm (Moody 1944).
Add the K of each bend, valve, entry and exit; for example 90° long-radius bend 0.2–0.3, gate valve open 0.15, globe valve 6–10, exit 1.

Results

Total pressure drop26.178kPa
Head loss2.6742m
Friction in straight pipe26.178kPa
Velocity1.6898m/s
Reynolds number172,207
Darcy friction factor0.018792
Relative roughness4.3988e-04

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Water 50 m³/h in DN100 (102.3 mm), 100 m, steel 0.045 mm. The inputs, in the units selected above:

InputValue
Volume flow50.000 m³/h
Pipe inside diameter102.30 mm
Pipe length100.00 m
Absolute roughness of the pipe wall0.045000 mm
Fluid density998.20 kg/m³
Dynamic viscosity1.0020 cP
Sum of fitting loss coefficients (0 = straight pipe only)0 -

Applying the formula below gives:

ResultValue
Total pressure drop26.178 kPa
Head loss2.6742 m
Friction in straight pipe26.178 kPa
Velocity1.6898 m/s
Reynolds number172,207
Darcy friction factor0.018792
Relative roughness4.3988e-04

Open this example in the calculator and change any input.

Formula

\(\Delta p = \left(f\,\frac{L}{D} + \Sigma K\right)\frac{\rho\,v^2}{2} \qquad v = \frac{4Q}{\pi D^2} \qquad Re = \frac{\rho\,v\,D}{\mu} \qquad h_L = \frac{\Delta p}{\rho\,g}\)

\(f = \frac{64}{Re}\ \ (Re < 2300) \qquad \frac{1}{\sqrt f} = -2\log_{10}\!\left(\frac{\varepsilon/D}{3.7} + \frac{2.51}{Re\sqrt f}\right)\ \ (Re \ge 2300)\)

Variables

Symbol Meaning SI unit
\(Q\) volume flow m³/s
\(D\) pipe inside diameter m
\(L\) pipe length m
\(\varepsilon\) absolute roughness of the wall m
\(\rho\) fluid density kg/m³
\(\mu\) dynamic viscosity Pa·s
\(\Sigma K\) sum of fitting loss coefficients –
\(\Delta p\) total pressure drop Pa
\(h_L\) head loss m
\(\Delta p_f\) friction in straight pipe Pa
\(\Delta p_K\) loss in fittings Pa
\(v\) mean velocity m/s
\(Re\) Reynolds number –
\(f\) Darcy friction factor –
\(\varepsilon/D\) relative roughness –
\(g\) standard gravity, 9.806 65 m/s²

Method and standards

Darcy–Weisbach equation with the Darcy friction factor from the Colebrook–White equation (C.F. Colebrook, 1939), the basis of the Moody chart (L.F. Moody, 1944), solved by iteration to full precision; laminar flow uses the exact 64/Re. Roughness values in the help text are Moody's.

Where it is used

  • Pump head calculations.
  • Checking lines for flow increases.
  • Comparing pipe sizes and materials.

Common mistakes

  • Using the laminar friction factor in turbulent flow, or the reverse.
  • Forgetting fittings, valves and elevation.
  • Using absolute roughness in the wrong unit.

Assumptions and limits

  • Incompressible, isothermal, fully developed flow in a full circular pipe. For gases it holds while the drop is under about 10 % of the absolute pressure.
  • Between Re 2 300 and 4 000 the flow is in transition; the turbulent value is shown and is conservative.
  • No static head: add ρ·g·Δz for a change of elevation.
  • For a rectangular duct use its equivalent diameter.

References

  • Darcy–Weisbach equation
  • Colebrook (1939)
  • Moody (1944)

Questions and answers

How is pressure drop in a pipe calculated?

Δp = f·(L/D)·ρv²/2. For 50 m³/h of water in a DN100 steel pipe (102.3 mm bore) the velocity is 1.69 m/s, Re = 172 000, f = 0.0188 and the drop over 100 m is 26.2 kPa (2.67 m of water).

Which friction factor is this?

The Darcy (Moody) friction factor: 64/Re in laminar flow and the Colebrook–White equation in turbulent flow. The Fanning factor used in some chemical engineering texts is one quarter of it.

How do I include bends and valves?

Add their loss coefficients K and enter the sum; each adds K·ρv²/2.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.