Worked example
Example: 3 m tank, 4 m to empty, 50 mm sharp orifice. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tank inside diameter | 3.0000 m |
| Starting liquid level above the outlet | 4.0000 m |
| Final liquid level above the outlet | 0 m |
| Outlet orifice or nozzle diameter | 50.000 mm |
| Discharge coefficient | 61.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Draining time | 88.839 min |
| Initial outflow | 38.192 m³/h |
| Volume drained | 28.274 m³ |
Open this example in the calculator and change any input.
Formula
\(t = \frac{A_t}{C_d\,a}\sqrt{\frac{2}{g}}\left(\sqrt{h_1} - \sqrt{h_2}\right) \qquad Q_1 = C_d\,a\sqrt{2 g h_1} \qquad V = A_t (h_1 - h_2)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_t\) | tank diameter | m |
| \(h_1\) | starting level | m |
| \(h_2\) | final level | m |
| \(d\) | outlet diameter | m |
| \(C_d\) | discharge coefficient | – |
| \(t\) | draining time | s |
| \(Q_1\) | initial outflow | m³/s |
| \(V\) | volume drained | m³ |
| \(A_t, a\) | tank and outlet areas | m² |
| \(g\) | standard gravity | m/s² |
Method and standards
Torricelli's law integrated over the falling level of a constant-area tank.
Where it is used
- Emergency draining of tanks.
- Batch transfer times.
- Fire water and storage tank checks.
Common mistakes
- Using the level above the floor instead of above the outlet.
- Cd of 1 for a sharp hole.
- Closed tanks without a vent.
Assumptions and limits
The velocity of the falling liquid surface is neglected: the exact Torricelli result divides the outflow velocity by √(1 − (C_d a/A_t)²). The error is below 1 % while the outlet is under about 0.3 of the tank diameter; the page warns above that.
Vented tank; discharge to atmosphere; quasi-steady flow.
References
- Torricelli's law with a discharge coefficient
Questions and answers
How long does a 3 m tank take to drain 4 m through a 50 mm orifice?
About 89 minutes with Cd 0.61; the first flow is 38 m³/h and it drains 28.3 m³.
Why does it slow down?
Outflow goes with the square root of the head, so the last metre takes longest.
Does outlet piping matter?
Yes; pipe friction lowers the flow. Use an effective Cd for the whole outlet.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.