Worked example
Example: Round 50 mm at 20 m/s, 2 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Jet type | Round nozzle |
| Nozzle diameter or slot width | 50.000 mm |
| Jet exit velocity | 20.000 m/s |
| Distance from the nozzle | 2.0000 m |
| Distance from the centreline | 0.10000 m |
| Round-jet constant | 6.2 (V₀ 10–50 m/s) |
| Kinematic viscosity (for Rushton) | 15.000 cSt |
Applying the formula below gives:
| Result | Value |
|---|---|
| Centreline velocity | 3.1000 m/s |
| Velocity at the off-axis distance | 2.4624 m/s |
| Flow ratio (jet plus entrained) | 12.800 |
| Total flow at x (per metre of slot length for a slot) | 1,809.6 m³/h |
| Centreline velocity by Rushton (round jets) | 3.1580 m/s |
Open this example in the calculator and change any input.
Formula
\(\frac{V_c}{V_0} = K\frac{D_0}{x}, \quad \log\frac{V_c}{V_r} = 40\left(\frac{r}{x}\right)^2, \quad \frac{q}{q_0} = 0.32\frac{x}{D_0}\ \text{(round)}\)
\(\frac{V_c}{V_0} = 2.28\left(\frac{B_0}{x}\right)^{0.5}, \quad \log\frac{V_c}{V_y} = 18.4\left(\frac{y}{x}\right)^2, \quad \frac{q}{q_0} = 0.62\left(\frac{x}{B_0}\right)^{0.5}\ \text{(slot)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{type}\) | Jet type | - |
| \(D_0\) | Nozzle diameter or slot width | m |
| \(V_0\) | Jet exit velocity | m/s |
| \(x\) | Distance from the nozzle | m |
| \(r\) | Distance from the centreline | m |
| \(K\) | Round-jet constant | - |
| \(\nu\) | Kinematic viscosity (for Rushton) | m²/s |
| \(V_c\) | Centreline velocity | m/s |
| \(V_r\) | Velocity at the off-axis distance | m/s |
| \(q/q_0\) | Flow ratio (jet plus entrained) | - |
| \(q\) | Total flow at x (per metre of slot length for a slot) | m³/s |
| \(V_{c,Rushton}\) | Centreline velocity by Rushton (round jets) | m/s |
Method and standards
Free-jet correlations.
Where it is used
- Air throw and mixing jets.
- Overfire air and burner jet penetration (first estimate).
Common mistakes
- Using it close to the nozzle (potential core).
- Ignoring walls and cross-flow.
Assumptions and limits
- Free jets into still fluid of the same density.
- Rushton (round jets only): V_c/V₀ = 1.41 (V₀D₀/ν)^0.135 D₀/x. The centreline velocity is capped at V₀ near the nozzle and q/q₀ at 1.
- For a slot the flow is per metre of slot length.
References
- Perry's Chemical Engineers' Handbook
- 9th ed. (McGraw-Hill, 2019)
- sec. 6
- Table 6-7 (turbulent free jets) and Eq. (6-110) (Rushton, AIChE J. 26: 1038, 1980)
Questions and answers
Why does the jet slow down?
It entrains still surrounding fluid; momentum is conserved, so the growing mass flow moves more slowly.
How far does entrainment go?
At 50 diameters a round jet carries about 16 times its own flow.
Where is this used?
Air distribution, furnace and burner jets, tank mixing eductors and spray cooling.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.