Worked example
Example: 100 m³/h: 200 m of DN100 and 300 m of DN80. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total flow | 100.00 m³/h |
| Length of branch 1 | 200.00 m |
| Diameter of branch 1 | 102.30 mm |
| Length of branch 2 | 300.00 m |
| Diameter of branch 2 | 77.900 mm |
| Pipe roughness | 0.045000 mm |
| Fluid density | 998.00 kg/m³ |
| Dynamic viscosity | 0.001000 Pa·s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow in branch 1 | 71.790 m³/h |
| Flow in branch 2 | 28.210 m³/h |
| Common pressure drop | 104.19 kPa |
| Share in branch 1 | 71.790 % |
Open this example in the calculator and change any input.
Formula
\(\Delta p = f_1 \frac{L_1}{d_1}\frac{\rho v_1^2}{2} = f_2 \frac{L_2}{d_2}\frac{\rho v_2^2}{2}, \quad Q_1 + Q_2 = Q\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Total flow | m³/s |
| \(L_1\) | Length of branch 1 | m |
| \(d_1\) | Diameter of branch 1 | m |
| \(L_2\) | Length of branch 2 | m |
| \(d_2\) | Diameter of branch 2 | m |
| \(\varepsilon\) | Pipe roughness | m |
| \(\rho\) | Fluid density | kg/m³ |
| \(\mu\) | Dynamic viscosity | Pa·s |
| \(Q_1\) | Flow in branch 1 | m³/s |
| \(Q_2\) | Flow in branch 2 | m³/s |
| \(\Delta p\) | Common pressure drop | Pa |
| \(Q_1/Q\) | Share in branch 1 | - |
Method and standards
Bisection on the split until the drops match.
Where it is used
- Bypass lines and loops.
- Cooling water distribution.
Common mistakes
- Assuming equal split.
- Ignoring fittings.
Assumptions and limits
- Incompressible, steady flow.
- The friction factor jumps from 64/Re to Colebrook at Re 2300; a branch between Re 2000 and 4000 gets a warning that the split is uncertain.
References
- Darcy–Weisbach with Colebrook friction factor; equal pressure drop in parallel branches
Questions and answers
Why does the smaller branch get less than its area share?
Pressure drop rises roughly with v² and 1/d, so narrow pipes resist more per unit flow.
Must both branches have the same pressure drop?
Yes, they start and end at the same points.
What about valves in a branch?
Add their K as equivalent length to that branch.