Worked example
Example: 50 m³/h in 4-inch pipe, ΣK 6.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume flow | 50.000 m³/h |
| Pipe inside diameter | 102.30 mm |
| Sum of the K values of the fittings | 6.5000 - |
| Fluid density | 998.00 kg/m³ |
| Darcy friction factor of the pipe (for the equivalent length) | 0.019000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity | 1.6898 m/s |
| Velocity head | 0.14558 m |
| Head loss Σ K v²/2g | 0.94627 m |
| Pressure drop | 9.2612 kPa |
| Equivalent pipe length Σ K d/f | 34.997 m |
Open this example in the calculator and change any input.
Formula
\(h_L = \sum K\, \frac{v^2}{2g}, \quad \Delta p = \sum K\, \frac{\rho v^2}{2}, \quad L_e = \frac{\sum K\, d}{f}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Volume flow | m³/s |
| \(d\) | Pipe inside diameter | m |
| \(\Sigma K\) | Sum of the K values of the fittings | - |
| \(\rho\) | Fluid density | kg/m³ |
| \(f\) | Darcy friction factor of the pipe (for the equivalent length) | - |
| \(v\) | Velocity | m/s |
| \(v^2/2g\) | Velocity head | m |
| \(h_L\) | Head loss Σ K v²/2g | m |
| \(\Delta p\) | Pressure drop | Pa |
| \(L_e\) | Equivalent pipe length Σ K d/f | m |
Method and standards
Losses proportional to the velocity head.
Where it is used
- Pump head and line pressure drop.
- Comparing valve types.
Common mistakes
- Velocity of the wrong pipe size.
- Counting the exit loss twice.
Assumptions and limits
- Turbulent flow, K constant.
References
- Resistance coefficient method
- Δp = K ρ v²/2 (Textbook fluid mechanics (White, Fluid Mechanics))
Questions and answers
What do fittings with ΣK = 6.5 lose at 50 m³/h in a 4-inch pipe?
Velocity 1.69 m/s; head loss 0.95 m of water.
Where do K values come from?
Maker's data or published tables; a fully open gate valve is small, a globe valve large.
What is equivalent length?
The length of straight pipe with the same loss, K d / f.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.