Worked example
Example: Duct 600 x 400 mm, 2 m³/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Duct width | 600.00 mm |
| Duct height | 400.00 mm |
| Volume flow (0 = skip) | 7,200.0 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Equivalent diameter (same friction at the same flow) | 532.81 mm |
| Hydraulic diameter | 480.00 mm |
| Duct area | 0.24000 m² |
| Aspect ratio | 1.5000 |
| Velocity in the rectangular duct | 8.3333 m/s |
| Velocity in the equivalent round duct | 8.9699 m/s |
Open this example in the calculator and change any input.
Formula
\(D_e = \frac{1.30\,(a\,b)^{0.625}}{(a+b)^{0.25}} \qquad D_h = \frac{2\,a\,b}{a+b} \qquad A = a\,b \qquad AR = \frac{\max(a,b)}{\min(a,b)}\)
\(v = \frac{\dot V}{A} \qquad v_e = \frac{4\,\dot V}{\pi D_e^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(a\) | duct width | m |
| \(b\) | duct height | m |
| \(\dot V\) | volume flow | m³/s |
| \(D_e\) | equivalent diameter (same friction at the same flow) | m |
| \(D_h\) | hydraulic diameter | m |
| \(A\) | duct area | m² |
| \(AR\) | aspect ratio | – |
| \(v\) | velocity in the rectangular duct | m/s |
| \(v_e\) | velocity in the equivalent round duct | m/s |
Method and standards
R.G. Huebscher's equation (ASHVE Transactions, 1948), as given in the Duct Design chapter of the ASHRAE Handbook—Fundamentals, and the hydraulic diameter 4A/P.
Where it is used
- Duct pressure drop with round-duct friction charts.
- Converting duct sizes during layout.
- Fan and draught calculations.
Common mistakes
- Using hydraulic diameter where equal-friction equivalent diameter is meant, or the reverse.
- Very flat ducts outside the correlation range.
- Forgetting the actual velocity in the rectangular duct.
Assumptions and limits
- Huebscher's tests covered aspect ratios up to 8:1; beyond that the result is approximate.
- Same roughness and fluid in both ducts; turbulent flow.
- For pressure drop use D_e with the volume flow, or D_h with the true velocity; do not mix the two.
References
- Huebscher (1948)
- ASHRAE Handbook—Fundamentals (Duct Design)
Questions and answers
What is the equivalent diameter of a rectangular duct?
The round duct with the same friction loss per metre at the same volume flow: De = 1.30·(a·b)^0.625/(a+b)^0.25. A 600 × 400 mm duct is equivalent to a 533 mm round duct.
How is it different from the hydraulic diameter?
The hydraulic diameter 2ab/(a+b) gives the same friction at the same velocity; use it with the actual duct velocity. The Huebscher diameter gives the same friction at the same flow; use it with the flow in a round-duct friction chart or calculator.
Why is the velocity different in the equivalent duct?
The equivalent round duct has a smaller area than the rectangle, so the same flow moves faster in it. The friction per metre is nevertheless the same.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.