Worked example
Example: 2 m³/s at 1 Pa/m, galvanised. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow | 7,200.0 m³/h |
| Friction rate | 1.0000 Pa/m |
| Duct roughness | 0.090000 mm |
| Air density | 1.2000 kg/m³ |
| Air viscosity | 1.8100e-05 Pa·s |
| Rectangular aspect ratio | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Round duct diameter | 573.54 mm |
| Velocity | 7.7413 m/s |
| Reynolds number | 294,360 |
| Rectangular duct, long side | 752.99 mm |
| Rectangular duct, short side | 376.49 mm |
Open this example in the calculator and change any input.
Formula
\(\frac{\Delta p}{L} = \frac{f}{D}\frac{\rho v^2}{2}, \quad \frac{1}{\sqrt f} = -2\log_{10}\left(\frac{\varepsilon}{3.7D} + \frac{2.51}{Re\sqrt f}\right), \quad D_e = \frac{1.30(ab)^{0.625}}{(a + b)^{0.25}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow | m³/s |
| \(\Delta p/L\) | Friction rate, in Pa/m (1 in WC per 100 ft = 8.17 Pa/m) | - |
| \(\varepsilon\) | Duct roughness | m |
| \(\rho\) | Air density | kg/m³ |
| \(\mu\) | Air viscosity | Pa·s |
| \(a/b\) | Rectangular aspect ratio | - |
| \(D\) | Round duct diameter | m |
| \(v\) | Velocity | m/s |
| \(Re\) | Reynolds number | - |
| \(a\) | Rectangular duct, long side | m |
| \(b\) | Rectangular duct, short side | m |
Method and standards
Colebrook and Huebscher.
Where it is used
- Supply and return duct layout.
- Rectangular duct selection for ceiling space.
Common mistakes
- Mixing Pa/m and Pa/100 ft.
- Very flat rectangular ducts (aspect ratio above 4).
Assumptions and limits
- Fully developed turbulent flow; standard air.
- The friction rate is entered in Pa/m in every unit system; 1 in WC per 100 ft is 8.17 Pa/m.
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 21 (Darcy–Weisbach, Colebrook, Huebscher equivalent diameter, equal-friction method)
Questions and answers
What is the equal-friction method?
Every duct section is sized for the same pressure loss per metre, so the index run's loss is simply the friction rate times its length plus fittings.
Why not size by velocity?
Velocity sizing suits noise limits; equal friction keeps the pressure balance simpler on branched systems.
What do the defaults represent?
A main supply duct in galvanised steel at a friction rate of about 1 Pa/m.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.