Worked example
Example: Supply at 13 °C through a 40 °C roof void. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow | 6,000.0 m³/h |
| Duct width | 600.00 mm |
| Duct height | 400.00 mm |
| Length through the space | 30.000 m |
| Duct U-value (per outer surface area) | 0.80000 W/(m²·K) |
| Air temperature entering | 13.000 °C |
| Surrounding temperature | 40.000 °C |
| Air density | 1.2000 kg/m³ |
| Air specific heat | 1.0060 kJ/(kg·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air temperature leaving | 13.637 °C |
| Temperature change | 0.63651 K |
| Heat gained (negative: lost) | 1.2807 kW |
Open this example in the calculator and change any input.
Formula
\(T_2 = T_a + (T_1 - T_a)\exp\left(-\frac{U\,2(W + H)L}{\rho \dot V c_p}\right), \quad \dot Q = \rho \dot V c_p (T_2 - T_1)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow | m³/s |
| \(W\) | Duct width | m |
| \(H\) | Duct height | m |
| \(L\) | Length through the space | m |
| \(U\) | Duct U-value (per outer surface area) | W/(m²·K) |
| \(T_1\) | Air temperature entering | K |
| \(T_a\) | Surrounding temperature | K |
| \(\rho\) | Air density | kg/m³ |
| \(c_p\) | Air specific heat | J/(kg·K) |
| \(T_2\) | Air temperature leaving | K |
| \(\Delta T\) | Temperature change | K |
| \(\dot Q\) | Heat gained (negative: lost) | W |
Method and standards
Energy balance along the duct.
Where it is used
- Long supply ducts through hot roof spaces.
- Insulation decisions.
Common mistakes
- Linear approximation on long ducts.
- Inner instead of outer surface area.
Assumptions and limits
- Constant U and surroundings.
- The perimeter 2(W + H) uses the dimensions entered: with U per outer surface area, enter the outside (insulated) dimensions; thick insulation makes the outer perimeter noticeably larger than the sheet size.
References
- Incropera
- DeWitt
- Bergman and Lavine
- Fundamentals of Heat and Mass Transfer
- ch. 8 (mean temperature in a duct with a uniform external temperature, T₂ = T_a + (T₁ − T_a) exp(−UPL/ṁc_p))
Questions and answers
6000 m³/h at 13 °C through 30 m of a 40 °C roof void?
The air warms about 0.6 K: some 1.3 kW of gain.
Why exponential?
The driving difference shrinks as the air warms.
Bare duct?
With U 6 W/m²K the rise is several times larger.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.