FireCADCalc

Fan Heat Gain and Temperature Rise of the Air Stream

Heat added to an air stream by a fan from flow, total pressure rise and efficiencies, whether the motor is in the air stream, and the air temperature rise.

Inputs

Examples: AHU 20 000 m³/h, motor in the streamPlug fan, motor outside

Results

All the fan's shaft work ends up as heat in the air; the motor loss joins it only if the motor sits in the stream.

Shaft power7.9365kW
Motor input8.6266kW
Heat to the air8.6266kW
Air temperature rise1.2863K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: AHU 20 000 m³/h, motor in the stream. The inputs, in the units selected above:

InputValue
Air flow20,000 m³/h
Fan total pressure rise101.97 mmWC
Fan efficiency70.000 %
Motor efficiency92.000 %
Motor positionIn the air stream
Air density1.2000 kg/m³
Air specific heat1.0060 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Shaft power7.9365 kW
Motor input8.6266 kW
Heat to the air8.6266 kW
Air temperature rise1.2863 K

Open this example in the calculator and change any input.

Formula

\(P_s = \frac{\dot V \Delta p_t}{\eta_f}, \quad P_e = \frac{P_s}{\eta_m}, \quad \dot Q = P_e\ \text{(motor in the air stream)}\ \text{or}\ P_s\ \text{(motor outside)}, \quad \Delta T = \frac{\dot Q}{\rho c_p \dot V}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow m³/s
\(\Delta p_t\) Fan total pressure rise Pa
\(\eta_f\) Fan efficiency -
\(\eta_m\) Motor efficiency -
\(\text{motor}\) Motor position -
\(\rho\) Air density kg/m³
\(c_p\) Air specific heat J/(kg·K)
\(P_s\) Shaft power W
\(P_e\) Motor input W
\(\dot Q\) Heat to the air W
\(\Delta T\) Air temperature rise K

Method and standards

Energy balance.

Where it is used

  • AHU and ID/FD fan air temperature rise.
  • Cooling load completeness.

Common mistakes

  • Using static instead of total pressure.
  • Forgetting the motor in the stream.

Assumptions and limits

  • Steady state.

References

  • Energy balance: shaft power = V Δp / η_f
  • all dissipated in the air (ASHRAE Handbook—Fundamentals ch. 18)

Questions and answers

20,000 m³/h at 1000 Pa, 70 % fan, motor in the stream?

About 8.6 kW to the air: a rise of about 1.3 K.

Draw-through or blow-through?

Blow-through adds the heat before the coil, draw-through after it, changing the supply temperature.

Why include it?

On large AHUs it is several per cent of the cooling load.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.