Sol-Air Temperature and Heat Gain Through a Sunlit Wall or Roof

Sol-air temperature of a sunlit wall or roof from outdoor temperature, solar irradiance and absorptance, and the steady heat gain through it.

Inputs

Examples: Dark roof at noonLight west wall

Light colours about 0.3–0.5, dark colours 0.8–0.95.
ASHRAE uses about 63 W/m² for horizontal surfaces and 0 for vertical walls.

Results

Steady value: heavy walls and roofs delay and damp the peak, so the cooling load is lower and later.

Sol-air temperature64.235°C
Steady heat gain U A (T_sa − T_i)4.0235kW
Gain without the sun U A (T_o − T_i)1.1000kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Dark roof at noon. The inputs, in the units selected above:

InputValue
Outdoor air temperature35.000 °C
Total solar irradiance on the surface0.80000 kW/m²
Solar absorptance of the surface70.000 %
Outside surface coefficient17.000 W/(m²·K)
Long-wave sky correction ε ΔR0.063000 kW/m²
U-value0.50000 W/(m²·K)
Area200.00 m²
Indoor temperature24.000 °C

Applying the formula below gives:

ResultValue
Sol-air temperature64.235 °C
Steady heat gain U A (T_sa − T_i)4.0235 kW
Gain without the sun U A (T_o − T_i)1.1000 kW

Open this example in the calculator and change any input.

Formula

\(T_{sa} = T_o + \frac{\alpha E_t}{h_o} - \frac{\varepsilon\Delta R}{h_o}, \quad \dot Q = U A (T_{sa} - T_i)\)

Variables

Symbol Meaning SI unit
\(T_o\) Outdoor air temperature K
\(E_t\) Total solar irradiance on the surface W/m²
\(\alpha\) Solar absorptance of the surface -
\(h_o\) Outside surface coefficient W/(m²·K)
\(\varepsilon\Delta R\) Long-wave sky correction ε ΔR W/m²
\(U\) U-value W/(m²·K)
\(A\) Area m²
\(T_i\) Indoor temperature K
\(T_{sa}\) Sol-air temperature K
\(\dot Q\) Steady heat gain U A (T_sa − T_i) W
\(\dot Q_{air}\) Gain without the sun U A (T_o − T_i) W

Method and standards

Surface energy balance.

Where it is used

  • Roof loads of control rooms and cold stores.
  • Choosing cool roof coatings.

Common mistakes

  • Using it as the peak cooling load for heavy roofs.
  • ΔR on walls.

Assumptions and limits

  • Steady state.

References

  • Sol-air temperature T_sa = T_o + αE_t/h_o − εΔR/h_o (ASHRAE Handbook—Fundamentals ch. 18)

Questions and answers

Dark roof, 35 °C air, 800 W/m²?

Sol-air about 64 °C; a 200 m² roof at U 0.5 gains about 4 kW steady.

Why does colour matter so much?

Absorptance multiplies the solar term directly.

Why subtract ΔR for roofs?

A roof radiates to the cold sky; walls see the ground and other surfaces.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.