Worked example
Example: 150 + 30 kW, two boilers sharing. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Design space heat loss | 150.00 kW |
| Domestic hot water load (simultaneous) | 30.000 kW |
| Distribution losses | 5.0000 % |
| Pick-up (warm-up) margin | 15.000 % |
| Number of boilers | 2.0000 - |
| Arrangement | Load shared by all |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total boiler capacity | 217.35 kW |
| Capacity of each boiler | 108.67 kW |
| Installed capacity | 217.35 kW |
Open this example in the calculator and change any input.
Formula
\(Q_b = (Q_h + Q_{dhw})(1 + f_d)(1 + f_p), \quad Q_1 = \frac{Q_b}{n}\ \text{or}\ \frac{Q_b}{n - 1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_h\) | Design space heat loss | W |
| \(Q_{dhw}\) | Domestic hot water load (simultaneous) | W |
| \(f_d\) | Distribution losses | - |
| \(f_p\) | Pick-up (warm-up) margin | - |
| \(n\) | Number of boilers | - |
| \(\text{arrangement}\) | Arrangement | - |
| \(Q_b\) | Total boiler capacity | W |
| \(Q_1\) | Capacity of each boiler | W |
| \(Q_{inst}\) | Installed capacity | W |
Method and standards
Load summation.
Where it is used
- New and replacement boiler plant.
- Standby planning.
Common mistakes
- Adding margins on margins.
- Sizing to connected radiator ratings instead of heat loss.
Assumptions and limits
- Peak loads coincident.
- The distribution and pick-up margins are compounded (multiplied), (1 + f_d)(1 + f_p), which is slightly larger than adding them.
References
- Load summation with margins (CIBSE Guide B1 approach)
Questions and answers
Why add a pick-up margin?
Intermittently heated buildings need extra output to warm up in a reasonable time after night set-back.
Why two or more boilers?
Part load is most of the season; several modules keep each boiler loaded efficiently and give standby.
What do the defaults represent?
A medium building with a hot-water load and two boilers sharing the load.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.