Room Pressurisation: Leakage Air Flow

Air leaking through gaps from a room held at a pressure difference (control rooms, clean rooms), from leakage area and discharge coefficient.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Control room 0.05 m² at 15 PaStair core 0.3 m² at 50 Pa

Results

Orifice flow through door gaps, cable openings and joints. Supply must exceed exhaust by this flow to hold the pressure; add 10–20 % margin. Door opening breaks the pressure briefly.

Leakage air flow549.00m³/h
Leakage as air changes per hour2.7450
Ideal jet velocity through the gaps √(2Δp/ρ)5.0000m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Control room 0.05 m² at 15 Pa. The inputs, in the units selected above:

InputValue
Total leakage area0.050000 m²
Pressure difference15.000 Pa
Discharge coefficient0.61000 -
Air density1.2000 kg/m³
Room volume200.00 m³

Applying the formula below gives:

ResultValue
Leakage air flow549.00 m³/h
Leakage as air changes per hour2.7450
Ideal jet velocity through the gaps √(2Δp/ρ)5.0000 m/s

Open this example in the calculator and change any input.

Formula

\(v = \sqrt{\frac{2\Delta p}{\rho}}, \quad \dot V = C_dA_Lv, \quad ACH = \frac{3600\,\dot V}{V}\)

Variables

Symbol Meaning SI unit
\(A_L\) Total leakage area m²
\(\Delta p\) Pressure difference Pa
\(C_d\) Discharge coefficient -
\(\rho\) Air density kg/m³
\(V\) Room volume m³
\(\dot V\) Leakage air flow m³/s
\(ACH\) Leakage as air changes per hour -
\(v\) Ideal jet velocity through the gaps m/s

Method and standards

Orifice equation.

Where it is used

  • Control and MCC room pressurisation.
  • Clean room supply excess.

Common mistakes

  • Ignoring cable trenches and ducts.
  • Designing to zero leakage.

Assumptions and limits

  • Orifice flow; constant density.
  • v is the ideal (vena contracta) jet velocity; the mean velocity over the leakage area A_L is C_d v.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 16 (orifice equation for leakage); ASHRAE Handbook—HVAC Applications (2019)
  • ch. 19 (clean spaces)

Questions and answers

Why pressurise a room?

To keep dust, fumes or corrosive gases out of control rooms, MCC rooms and clean areas.

How much pressure is enough?

Typically 10–15 Pa between clean areas, 25–50 Pa for stair cores in fire mode.

What do the defaults represent?

A control room with door and cable gaps held at 15 Pa.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.