Radiator Output at Other Water and Room Temperatures

Heat output of a radiator or convector at actual flow, return and room temperatures from its rated output at the standard temperature difference and its exponent.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 1.5 kW panel at 55/45/20 °CConvector 2 kW at 70/50/18 °C

Results

EN 442 rating at 75/65/20 °C (ΔT = 49.8 K, nominally 50 K) and Q = Q_n(ΔT/ΔT_n)^n; n is about 1.3 for panel radiators and 1.4 for convectors. Low-temperature systems (heat pumps) need much larger radiators.

Log-mean temperature difference29.720K
Actual output762.77W
Output factor50.852%
Water flow65.599kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1.5 kW panel at 55/45/20 °C. The inputs, in the units selected above:

InputValue
Rated output1,500.0 W
Rated temperature difference (EN 442: 50 K)50.000 K
Radiator exponent1.3000 -
Flow temperature55.000 °C
Return temperature45.000 °C
Room temperature20.000 °C

Applying the formula below gives:

ResultValue
Log-mean temperature difference29.720 K
Actual output762.77 W
Output factor50.852 %
Water flow65.599 kg/h

Open this example in the calculator and change any input.

Formula

\(\Delta T_{ln} = \frac{t_f - t_r}{\ln\frac{t_f - t_a}{t_r - t_a}}, \quad Q = Q_n\left(\frac{\Delta T_{ln}}{\Delta T_n}\right)^n, \quad \dot m = \frac{Q}{c_w (t_f - t_r)}\)

Variables

Symbol Meaning SI unit
\(Q_n\) Rated output W
\(\Delta T_n\) Rated temperature difference (EN 442: 50 K) K
\(n\) Radiator exponent -
\(t_f\) Flow temperature K
\(t_r\) Return temperature K
\(t_a\) Room temperature K
\(\Delta T_{ln}\) Log-mean temperature difference K
\(Q\) Actual output W
\(Q/Q_n\) Output factor -
\(\dot m\) Water flow kg/s
\(c_w\) Specific heat of water, 4 186 J/(kg·K)

Method and standards

EN 442 characteristic.

Where it is used

  • Heat pump retrofits.
  • Checking emitters at lower flow temperatures.

Common mistakes

  • Using arithmetic mean temperature at low ΔT ratios.
  • Ignoring the exponent.

Assumptions and limits

  • Steady output; rated exponent.

References

  • EN 442-2 characteristic equation Q = K_mΔT^n with the logarithmic temperature difference

Questions and answers

Why does a radiator give less at heat-pump temperatures?

At 55/45/20 °C the log-mean difference is about 30 K instead of 50 K; with n = 1.3 output falls to about half.

Why use the logarithmic difference?

Water cools along the radiator; the log-mean difference is what the rating method uses.

What do the defaults represent?

A 1.5 kW (rated) panel radiator run at 55/45 °C in a 20 °C room.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.