Worked example
Example: 40 cars, 180 g/h each, 35 ppm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cars moving at the peak | 40.000 - |
| CO emission per moving car | 180.00 g/h |
| CO limit | 35.000 ppm |
| CO in outdoor air | 2.0000 ppm |
| Air temperature | 20.000 °C |
| Car park volume | 15,000 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| CO generation | 7,200.0 g/h |
| Allowed rise above outdoor | 38.426 mg/m³ |
| Ventilation air flow | 187,376 m³/h |
| Air changes per hour | 12.492 |
Open this example in the calculator and change any input.
Formula
\(\dot V = \frac{NE}{(C_{lim} - C_o)\rho_{CO}}, \quad \rho_{CO} = \frac{pM_{CO}}{RT}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(N\) | Cars moving at the peak | - |
| \(E\) | CO emission per moving car | kg/s |
| \(C_{lim}\) | CO limit | - |
| \(C_o\) | CO in outdoor air | - |
| \(T\) | Air temperature | K |
| \(p\) | Air pressure, standard atmosphere 101 325 Pa | Pa |
| \(M_{CO}\) | Molar mass of CO, 28.010 kg/kmol | kg/kmol |
| \(R\) | Universal gas constant, 8 314.462 618 J/(kmol·K) | J/(kmol·K) |
| \(\rho_{CO}\) | Density of pure CO at p and T | kg/m³ |
| \(V\) | Car park volume | m³ |
| \(G\) | CO generation | kg/s |
| \(\Delta C\) | Allowed rise above outdoor | kg/m³ |
| \(\dot V\) | Ventilation air flow | m³/s |
| \(ACH\) | Air changes per hour | - |
Method and standards
Steady dilution.
Where it is used
- Basement car parks in commercial buildings.
- Loading bays.
Common mistakes
- Using old fleet emission factors.
- Ignoring short-circuiting between supply and exhaust.
Assumptions and limits
- Well mixed; steady state.
- The ppm-to-mass conversion is at one standard atmosphere (101 325 Pa).
References
- ASHRAE Handbook—HVAC Applications (2019)
- ch. 16 (enclosed vehicular facilities: dilution of CO)
Questions and answers
Why CO and not other exhaust gases?
CO is the traditional design pollutant for petrol vehicles; diesel fleets may need NO₂ as well.
Can demand control save energy?
Yes: CO sensors let fans run slow most of the day and full only at peaks.
What do the defaults represent?
40 cars moving at once in a basement car park with a 35 ppm limit.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.